Current Transducer LAH 100-P
IPN = 100 A
For the electronic measurement of currents : DC, AC, pulsed ...,
with a galvanic isolation between the primary circuit
(high power) and the secondary circuit (electronic circuit).
16052
Electrical data
IPN
IP
RM
Primary nominal r.m.s. current
Primary current, measuring range
Measuring resistance @
100
0 .. 160
TA = 70°C
RM min RMmax RM min RMmax
A
A
Features
1)
TA = 85°C
· Closed loop (compensated) current
transducer using the Hall effect
· Printed circuit board mounting
· Insulated plastic case recognized
according to UL 94-V0.
with ± 12 V
with ± 15 V
@ IPN [± A DC
@ IPN [A RMS
@ IPN [± A DC
]
0
0
63
11
0
0
57
5
W
W
W
W
2)
]
]
2)
20 120 45 114
20 51 45 45
@ IPN [A RMS
@ IP < IPN
]
3)
Advantages
ISN
KN
VC
IC
Vd
Ve
Vw
Secondary nominal r.m.s. current
Conversion ratio
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn
R.m.s. voltage for partial discharge extinction @ 10 pC > 2
50
1 : 2000
± 12 .. 15
10 (@ ± 15 V)+IS mA
mA
V
· Excellent accuracy
· Very good linearity
· Low temperature drift
· Optimized response time
· Wide frequency bandwidth
· No insertion losses
· High immunity to external
interference
5
kV
kV
kV
Impulse withstand voltage 1.2/50 µs
> 12
Accuracy - Dynamic performance data
X
Accuracy4) @ IPN, TA = 25°C
Linearity error
± 0.25
< 0.15
%
%
· Current overload capability.
e
L
Applications
Typ Max
IO
IOM
IOT
Offset current @ TA = 25°C
Residual current@ IP = 0, after an overload of 5 x IPN ± 0.10 ± 0.15 mA
Thermal drift of IO
± 0.15 mA
· AC variable speed drives and servo
motor drives
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptible Power Supplies
(UPS)
0°C .. + 70°C
- 25°C .. + 85°C
± 0.10 ± 0.40 mA
± 0.10 ± 0.50 mA
tr a
tr
Reaction time @ 10 % of IPN
Response time 5) @ 90 % of IPN
< 200
< 500
> 200
ns
ns
di/dt di/dt accurately followed
f
A/µs
kHz
· Switched Mode Power Supplies
(SMPS)
Frequency bandwidth (- 1 dB)
DC .. 200
General data
· Power supplies for welding
applications.
TA
TS
RS
Ambient operating temperature
Ambient storage temperature
Secondary coil resistance
- 25 .. + 85
- 40 .. + 90
115
121
I
°C
°C
W
@ TA = 70°C
@ TA = 85°C
W
Insulating material group
Mass
m
24
g
Standards
EN 50178 : 1997
1)
Notes : For 10 s, with RM £ 25 W (VC = ± 15 V) - 2) 50 Hz Sinusoidal -
3)
The measuring resistance RM min may be lower (see "LAH Technical
Information" leaflet) - 4) Without IO & IOM 5) With a di/dt of 100 A/µs.
-
060303/8
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
page1/2
LEM