Heavy current
INSERT 160A
https://www.schurter.com /PG13_14_15
Insert 160A, DIN00
See below:
Approvals and Compliances
Description
Characteristics
- With 3 x 1-pole fuse switch disconnector
- Protection 2-piece, transparent and sealable
- Partitioning between phase/phase and phase/N
- N-connector for TN-C to TN-S
- N-connector separating Piece self-opening when loosening the screw
- Neutral conductor screw: Tightening torque max. 2.5 Nm
- Glass fiber Polyester
- Difficult to burn
- Impact resistant
Weblinks
pdf data sheet, html datasheet, Detailed request for product
Technical Data
Rated Current Ie
160A @ 500VAC
Rated Impulse Withstand Vol- 8kV
tage Uimp
125A@ 690VAC
690VAC
1000VAC
50Hz
Conditioned Rated Short Cicuit 50kA @ 690VAC
Current
Rated voltage Ue
Rated isolation voltage Ui
Rated Power Operating Fre-
quency fe
80kA@ 500VAC
20kA @ 500VAC
Rated short-time withstand
current with fuse links
Allowed Ambient Temperature -25°C to +40°C acc. to IEC 61439
Protection by closed housing IP20
Terminals
NH-Fuse-Link with Prisms
6 - 95mm²
Neutral Disconnector with
Straps
6 - 95mm²
Earth Connection Bride
6 - 95mm²
Prisma strap: radius small 6 - 25 mm² / radius big 35 - 95 mm²
NH-Switch disconnector
Fuse-Link
Rated Current Ie
DIN 00
Category of use AC
Category of use DC
AC-23B @ 400VAC
AC-22B @ 500VAC
AC-21B @ 690VAC
DC-22B @ 220VDC
160A @ 500VAC
125A@ 690VAC
690VAC
Rated voltage Ue
220VDC
1000VAC
Rated power dissipation with- 2.3 W
out NH fuse-links at Ith
Rated isolation voltage Ui
Rated Power Operating Fre-
quency fe
Rated Impulse Withstand Vol- 8kV
tage Uimp
Protection class
Mechanical lifetime
Electrical lifetime
IP20
50Hz
1400 Insertions
200 Insertions
-40°C to +55
Ambient Temperature Tu**)
Conditioned Rated Short Cicuit 80kA @ 500VAC
Current
50kA @ 690VAC
**) A reduction of the rated current is required above 30°C
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about