Embedded Power for
Business-Critical Continuity
Rev. 7.9.09_77
iMP Series
ꢀ of 9
TM
Intelligent MP
Series
Up to 1500 Watts
Total Power: Up to 1500 Watts
Input Voltage: 85 - 264 Vac
120-300 Vdc
# of Outputs: Up to 21
Special Features
• Full Medical EN60601 approval**
• Intelligent I C control
Electrical Specifications
2
• Voltage adjustment on all outputs
2
(Manual or I C)
Input
• Configurable input and output
(case and module) OK signals and
indicators
Input range:
85 - 264 Vac 120 - 350 Vdc
(limited to 300 Vdc in medical applications)
• Configurable inhibit/enable
• Configurable output
UP/DOWN sequencing
• Configurable current limit
Frequency:
47 - 440 Hz
Inrush current:
Efficiency:
40 A peak max. (soft start)
Up to 85% @ full case load
(foldback or constant current)
• High power density (8.8 W/cu-in)
• Intelligent fan
(speed control/fault status)
• Downloadable GUI from website
• Customer provided air option
Power Factor:
Turn-on time:
0.99 typ. meets EN61000-3-2 (n/a @ 440 Hz)
AC on 2.0 sec typ., inhibit/enable 150 ms typical
Programmable delay; 50 ms internal turn-on delay (Dual Output only)
EMI filter:
CISPR 22/EN55022 Level “B”**
• uP controlled PFC input with active
Leakage current:
Radiated EMI:
Holdover storage:
300 µA max. @ 240 Vac; 47 - 63 Hz
inrush protection
2
• I C monitor of voltage, current, and
CISPR 22/EN55022 Level “B”**
temp
20 ms minimum (independent of input Vac) additional 34ms holdover
storage with optional HUP module
• Programmable voltage, current limit,
2
inhibit/enable through I C
(SEMI F47 compatible). For iMP4 15 ms (low-line), 10 ms (high-line)
• Optional extended hold-up module
(SEMI F47 compliance)
• Increased power density to 50% over
standard MP
AC OK:
> 5 ms early warning min. before outputs lose regulation
Full cycle ride thru (50 Hz) (n/a on iMP4 > 750 W @ 90 Vac)
Harmonic distortion: Meets EN61000-3-2
• External switching frequency sync
input
• Optional conformal coating
• Industrial temp range (-40 ºC to 70 ºC)
• No preload required
Isolation:
Meets EN60950 and EN60601
Global Inhibit/Enable: TTL, Logic “1” and Logic “0”; configurable
Input fuse (internal): iMP4: 16 A; iMP8: 20 A; iMP1: 25 A (both lines fused)
• Industrial shock/vibration (> 50G’s)
Warranty:
2 years
Safety
•
•
•
•
UL
UL60950/UL2601**
CSA22.2 No. 234 Level 5
EN60950/EN60601-1**
** iMP1 requires factory modification for medical leakage. This modification reduces EMI to level A.
CSA
VDE
BABT Compliance to
EN60950/EN60601 BS7002
•
•
CB
CE
Certificate and report
Mark to LVD