描述
Up to 1500 Watts

IMP8-3L0-2E2-1Q1-4LL021-A 数据手册

 浏览型号IMP8-3L0-2E2-1Q1-4LL021-A的Datasheet PDF文件第2页浏览型号IMP8-3L0-2E2-1Q1-4LL021-A的Datasheet PDF文件第3页浏览型号IMP8-3L0-2E2-1Q1-4LL021-A的Datasheet PDF文件第4页浏览型号IMP8-3L0-2E2-1Q1-4LL021-A的Datasheet PDF文件第5页浏览型号IMP8-3L0-2E2-1Q1-4LL021-A的Datasheet PDF文件第6页浏览型号IMP8-3L0-2E2-1Q1-4LL021-A的Datasheet PDF文件第7页 
Embedded Power for  
Business-Critical Continuity  
Rev. 7.9.09_77  
iMP Series  
ꢀ of 9  
TM  
Intelligent MP  
Series  
Up to 1500 Watts  
Total Power: Up to 1500 Watts  
Input Voltage: 85 - 264 Vac  
120-300 Vdc  
# of Outputs: Up to 21  
Special Features  
Full Medical EN60601 approval**  
• Intelligent I C control  
Electrical Specifications  
2
• Voltage adjustment on all outputs  
2
(Manual or I C)  
Input  
• Configurable input and output  
(case and module) OK signals and  
indicators  
Input range:  
85 - 264 Vac 120 - 350 Vdc  
(limited to 300 Vdc in medical applications)  
• Configurable inhibit/enable  
• Configurable output  
UP/DOWN sequencing  
• Configurable current limit  
Frequency:  
47 - 440 Hz  
Inrush current:  
Efficiency:  
40 A peak max. (soft start)  
Up to 85% @ full case load  
(foldback or constant current)  
• High power density (8.8 W/cu-in)  
• Intelligent fan  
(speed control/fault status)  
• Downloadable GUI from website  
• Customer provided air option  
Power Factor:  
Turn-on time:  
0.99 typ. meets EN61000-3-2 (n/a @ 440 Hz)  
AC on 2.0 sec typ., inhibit/enable 150 ms typical  
Programmable delay; 50 ms internal turn-on delay (Dual Output only)  
EMI filter:  
CISPR 22/EN55022 Level “B”**  
• uP controlled PFC input with active  
Leakage current:  
Radiated EMI:  
Holdover storage:  
300 µA max. @ 240 Vac; 47 - 63 Hz  
inrush protection  
2
• I C monitor of voltage, current, and  
CISPR 22/EN55022 Level “B”**  
temp  
20 ms minimum (independent of input Vac) additional 34ms holdover  
storage with optional HUP module  
• Programmable voltage, current limit,  
2
inhibit/enable through I C  
(SEMI F47 compatible). For iMP4 15 ms (low-line), 10 ms (high-line)  
• Optional extended hold-up module  
(SEMI F47 compliance)  
• Increased power density to 50% over  
standard MP  
AC OK:  
> 5 ms early warning min. before outputs lose regulation  
Full cycle ride thru (50 Hz) (n/a on iMP4 > 750 W @ 90 Vac)  
Harmonic distortion: Meets EN61000-3-2  
• External switching frequency sync  
input  
• Optional conformal coating  
• Industrial temp range (-40 ºC to 70 ºC)  
• No preload required  
Isolation:  
Meets EN60950 and EN60601  
Global Inhibit/Enable: TTL, Logic “1” and Logic “0”; configurable  
Input fuse (internal): iMP4: 16 A; iMP8: 20 A; iMP1: 25 A (both lines fused)  
• Industrial shock/vibration (> 50G’s)  
Warranty:  
2 years  
Safety  
UL  
UL60950/UL2601**  
CSA22.2 No. 234 Level 5  
EN60950/EN60601-1**  
** iMP1 requires factory modification for medical leakage. This modification reduces EMI to level A.  
CSA  
VDE  
BABT Compliance to  
EN60950/EN60601 BS7002  
CB  
CE  
Certificate and report  
Mark to LVD