Time Delay Relays
Dedicated - Single Shot
HRDS SERIES
Single ShotTimer
Description
The HRDS Series combines an electromechanical relay output
with microcontroller timing circuitry. It offers 12 to 230V
operation in five options and factory fixed, onboard or external
adjustable time delays with a repeat accuracy of 0.ꢀ5. The
output contact rating allows for direct operation of heavy loads,
such as compressors, pumps, blower motors, heaters, etc. This
series is ideal for OEM applications where cost is a factor.
Operation (Single Shot)
Input voltage must be applied before and during timing. Upon
momentary or maintained closure of the initiate switch, the
output relay energizes for a measured interval of time. At the
end of the delay, the output de-energizes. Opening or reclosing
the initiate switch during timing has no affect on the time delay.
The output will energize if the initiate switch is closed when
input voltage is applied.
Reset: Reset occurs when the time delay is complete and the
initiate switch is opened. Loss of input voltage resets the time
delay and output.
Wiring Diagram
Features & Benefits
L1
N/L2
FEATURES
BENEFITS
NO = Normally Open
S1 = Initiate Switch
L = Load
Microcontroller based
Repeat Accuracy + / - 0.5%
Compact, low
cost design
C = Common,Transfer Contact
Allows flexiblility for OEM applications
Isolated, 30A, SPDT,
NO output contacts
Allows direct operation of heavy loads:
compressors, pumps, blower moters, heaters.
NOTE: A knob, or terminals
4 & 5 are only included on
adjustable units. R is used
Encapsulated
Protects against shock, vibration, and humidity
T
when external adjustment is
ordered. Relay contacts are
not isolated.
Accessories
P1004-95, P1004-95-X Versa-Pot
Panel mountable, industrial potentiometer
recommended for remote time delay adjustment.
P1023-6 Mounting bracket
The 90° orientation of mounting slots makes
installation/removal of modules quick and easy.
P0700-7 Versa-Knob
Designed for 0.2ꢀ in (6.3ꢀ mm) shaft of
Versa-Pot. Semi-gloss industrial black finish.
Ordering Information
P1015-13 (AWG 10/12), P1015-64 (AWG 14/16)
Female Quick Connect
These 0.2ꢀ in. (6.3ꢀ mm) female terminals are
constructed with an insulator barrel to provide
strain relief.
MODEL
INPUT VOLTAGE ADJUSTMENT
TIME DELAY
0.1 - 10s
3m
HRDS120
HRDS313M
HRDS321
HRDS421
HRDS430
12VDC
24VDC
24VDC
120VAC
120VAC
Onboard
Fixed
Onboard
Onboard
External
1 - 100s
1 - 100s
0.1 - 10s
P1015-18 Quick Connect to Screw Adapter
Screw adapter terminal designed for use with
all modules with 0.2ꢀ in. (6.3ꢀ mm) male quick
connect terminals.
If you don’t find the part you need, call us for a custom product 800-843-8848
© 2016 Littelfuse Protection Relays & Controls
www.littelfuse.com/hrds
Rev: 1-A-062116