Current Transducer HAT 200..1500-S
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 200..1500 A
VOUT = ± 4 V
Electrical data
Primarynominal
r.m.s. current
IPN (A)
Primary current
measuring range 4)
IP (A)
Type
Features
200
400
500
600
750
± 600
HAT 200-S
HAT 400-S
HAT 500-S
HAT 600-S
HAT 750-S
HAT 800-S
HAT 1000-S
HAT 1200-S
HAT 1500-S
± 1200
± 1500
± 1800
± 2250
± 2400
± 3000
± 3000
± 3000
· Hall effect measuring principle
· Galvanic isolation between primary
and secondary circuit
· Isolation voltage 3000 V
· Low power consumption
· Extended measuring range(3 x IPN
· Insulated plastic case recognized
according to UL 94-V0
800
1000
1200
1500
)
VC
IC
RIS
VOUT
ROUT
RL
Supply voltage (± 5 %)4)
Current consumption
Isolation resistance @ 500 VDC
Output voltage @ ± IPN, RL = 10 kW, TA = 25°C
Output internal resistance
± 15
± 15
> 1000
± 4
100
> 10
V
mA
MW
V
W
kW
Advantages
Load resistance
· Easy mounting
· Small size and space saving
· Only one design for wide current
ratings range
· High immunity to external
interference.
Accuracy-Dynamic performance data
X
e
Accuracy @ IPN, TA = 25°C (without offset)
Linearity error1) (0 .. ± IPN)
< ± 1 % of IPN
< ± 1 % of IPN
L
VOE
VOH
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x IPN
< ± 20
mV
< ± 10
< ± 1
< ± 0.1
< 5
mV
mV/K
%/K
µs
Applications
VOT
TCe
tr
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth 2) (- 3 dB)
· DC motor drives
· Switched Mode Power Supplies
(SMPS)
G
f
DC .. 25
kHz
· AC variable speed drives
· Uninterruptible Power Supplies
(UPS)
· Battery supplied applications
· Power supplies for welding
applications
General data
TA
TS
Ambient operating temperature
Ambient storage temperature HAT 200-S, HAT 500..1500-S - 15 .. + 85 °C
HAT 400-S - 25 .. + 85 °C
Mass
UL94 classification
- 10 .. + 80 °C
m
300
V0
g
Notes : 1) Linearity data exclude the electrical offset.
2) Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency.
3)
Please consult characterisation report for more technical details and
application advice.
4) Operating at ±12V £ Vc < ±15V will reduce the measuring range.