Current Transducers HAC 100..800-S
IPN = 100 .. 800 A
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
Features
Primarynominal
current rms
IPN (A)
Primary current
measuring range
IPM (A)
Type
RoHS since
date code
· Hall effect measuring principle
· Galvanic isolation between primary
and secondary circuit
· Isolation voltage 2500 V
· Low power consumption
100
200
300
400
500
600
800
± 300
± 600
± 900
± 1200
± 1500
± 1800
± 1800
HAC 100-S
HAC 200-S
HAC 300-S
HAC 400-S
HAC 500-S
HAC 600-S
HAC 800-S
46256
46220
planned
46242
planned
46186
46219
· Extended measuring range (3 x IPN)
VC
IC
Supply voltage (± 5 %)
± 15
V
mA
mA
MW
V
Advantages
Current consumption HAC 100..300-S
HAC 400..800-S
< ± 18
< ± 25
> 1000
· Easy mounting
· Small size and space saving
· Only one design for wide current
ratings range
· High immunity to external
interference.
RIS
Isolation resistance @ 500 VDC
VOUT
ROUT
RL
Output voltage (Analog) @ ± IPN, RL = 10 kW, TA = 25°C ± 4
Output internal resistance
Load resistance
100
W
> 10
kW
Accuracy - Dynamic performance data
Applications
X
Accuracy @ IPN, TA = 25°C (excluding offset)
< ± 1 % of IPN
< ± 1 % of IPN
e
Linearity error (0 .. ± IPN)
· AC variable speed drives
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptible Power Supplies
(UPS)
· Switched Mode Power Supplies
(SMPS)
· Power supplies for welding
applications.
L
VOE
VOH
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x IPN
< ± 30
mV
< ± 35
< ± 1
mV
mV/K
%/K
ms
TCVOE
TCVOUT
tr
Temperature coefficient of VOE
Temperature coefficient of VOUT (% of reading)
Response time to 90% of IPN step
Frequency bandwidth (- 3 dB)1)
< ± 0.1
< 7
BW
DC .. 50
kHz
General data
Applicationdomain
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
- 10 .. + 80 °C
- 15 .. + 85 °C
· Industrial
70
g
Note :
1) Derating is needed to avoid excessive core heating at high frequency.
Page 1/3
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
061114/7
www.lem.com