GLC75 Commercial/GLM75 Medical
75Watt Single Output Global Performance Switchers
FEATURES:
• Cost-effective single-output power source
• 3.4" x 5.75" x 1.56" (meets 1U applications)
• Universal input 90-264 Vac
• 2-year warranty
• Power fail detect
• Commercial Approved to UL1950, CSA22.2 No. 234
and IEC950, EN60950
• Medical Approved to UL2601-1, IEC601-1
and CSA22.2 No. 601
marked to LVD
•
SPECIFICATIONS:
Ac Input
90-264 Vac, 47-63 Hz single phase.
Input Protection
Internal ac fuse provided. Designed to blow only if a
catastrophic failure occurs in the unit—fuse does not blow
on overload or short circuit.
Input Current
Maximum input current at 120 Vac, 60 Hz with full rated
output load not to exceed 2.3 A.
Inrush Current
Inrush limited by internal thermistors. Inrush at 240 Vac,
averaged over the first ac half-cycle under cold start
conditions will not exceed 37 A.
Output Power
Normal continuous output power is 75 W for unrestricted
natural convection cooling; 110 W with 26 cfm airflow.
During peak load conditions output regulation may exceed
total regulation and noise limits.
Temperature Coefficient
0.03%/°C typical on all outputs.
Power Fail
Output Regulation
A standard TTL or CMOS compatible output goes low (<
0.5 V) 5ms before output voltage drops more than 4%
below nominal voltage upon loss of ac power. Signal is
factory set to trip on 84 to 94 Vac brown-out depending
upon incoming line impedance and distortion. Other
settings are available through adjustment of built-in
potentiometer (consult factory for assistance). Output will
stay low for 20 ms minimum.
Regulation measured by changing from 5% to 50% load or
50% load to full load in either direction.
Power Limit
Factory set to begin power limiting at approximately 120 W
(GLC 75-5 is set at approximately 100 W). Fully protected
against short circuit and output overload. Short circuit
protection is cycling type power limit.
EMI/EMC Compliance
All models include built-in EMI filtering to meet the
following emissions requirements:
EMI SPECIFICATIONS
Conducted Emissions - GLC75-EN55022 Class B; FCC Class B
Conducted Emissions - GLM75-EN55011 Class B; FCC Class B
Output Noise
0.5% rms, 1% pk-pk, 20 MHz bandwidth, differential mode.
Measured with noise probe directly across output termi-
nals of the power supply.
COMPLIANCE LEVEL
Transient Response
Static Discharge
EN61000-4-2, 6 kV contact, 8 kV air
EN61000-4-3, 3 V/meter
EN61000-4-4, 2 kV, 5 kHz
Main Output: 500 µs typical response time for return to
within 0.5% of final value for a 50% load step change, Di/
Dt<0.2 A/µs. Maximum voltage deviation is 3.5%. Startup/
shutdown overshoot less than 3%.
RF Field Susceptibility
Fast Transients/Bursts
Surge Susceptibility
EN61000-4-5, 1 kV diff., 2 kV com.
Commercial Safety
Overvoltage Protection
Standard on all models.
All GLC models are approved to UL1950, CSA22.2 No.
234 Level 3, IEC950 and EN60950. Consult factory for
approval status.
Voltage Adjust
Factory set on standard unit; however, potentiometer
adjusts voltage ±5% minimum. Consult factory for applica-
tion assistance.
Medical Leakage Current
70 µA 264 V @ 50 Hz (normal conditions).
Medical Safety
Efficiency
72-85% depending on model.
All GLM models are approved to UL2601, CSA22.2 No.
601, IEC601-1 and EN60601. Consult factory for approval
status.