Ordering information
Three phase input type(1-stage filter)
FTA -80 -683 -O
FTA series(80,100,125,150A)
1
2
3
4
1Model Name
2Rated Current
3Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
R
Leakage Current
Line to ground
Code (Input 250/500V 60Hz) capacitor
(155,335only 250/400V 60Hz) (nominal value)
223
683
104
155
335
1.0mA/2.0mA max
2.5mA/5.0mA max
3.5mA/7.0mA max
160mA/250mA max
320mA/500mA max
22,000pF
68,000pF
100,000pF
1.5 F
3.3 F
*
When the line to ground capacitor code is
different, the attenuation characteristic is different.
4Option
H:Ultra high attenuation type
"155","335" is not applied.
S:Hexagon socket head cap screw
(Standard type is Hexagon head screw)
U:Improve differential mode attenuation
(Rated voltage 250V)
G:With switch of line to ground capacitor
Only "155","335" is applied.
Features of FTA series
Book type (Space-saving type)
-1-stage filter General-purpose High-attenuation (150kHz - 1MHz)
-Selectable leakage current value, Ultra high attenuation type
"155","335" for EU
"155" is Leakage current 160mA/250mA max
when the switch state is ON (switched to “ ”).
50μA/80μA max when the switch state is OFF
*
(switched to
“ ”).
(Wye type with neutral earth system), With switch of line to ground capacitor "-G"
"335" is Leakage current 320mA/500mA max
when the switch state is ON (switched to “ ”).
50μA/80μA max when the switch state is OFF
(switched to “ ”).
Specifications
No.
1
2
Items
Rated Voltage[V]
Rated Current[A]
FTA-80-683
AC Three phase 500 (voltage range:528 max) 50/60Hz *1 *2
80 100 125
FTA-100-683
FTA-125-683
FTA-150-683
150
3
4
5
6
Test Voltage (Terminal-Mounting Plate)
Isolation Resistance (Terminal-Mounting Plate)
Leakage current 250/500V 60Hz
DC resistance
2,500 VAC (Cutoff Current = 100mA), 1minute at room temperature and humidity *3
500 VDC 100MWmin at room temperature and humidity *4
2.5mA/5.0mA max
5mWmax
4mWmax
3mWmax
3mWmax
7
8
9
Safety agency approval temperatures
Operating temperature
Operating humidity
-25 to +85C(Refer to Derating Curve)
-40 to +85C(Refer to Derating Curve)
20 to 95%RH (Non condensing)
10
11
12
13
Storage temperature/humidity
Vibration
Impact
-40 to +85C/20 to 95%RH (Non condensing)
2
10 to 55Hz, 19.6m/s (2G), 3min. Period, 1hour each X, Y and Z axis
2
196.1m/s (20G), 11ms Once each X, Y and Z axis
Safety agency approvals
UL1283, CSA C22.2 No.8 (C-UL) , DIN EN60939 VDE0565 Teil3-1, ENEC
100X130X210 mm (WXHXD)
100X170X260 mm(WXHXD)
(Option: -G refer to external view)
(Option: -G refer to external view)
14
15
Case size (without projection)
[3.94X5.12X8.27 inches]
[3.94X6.69X10.24 inches]
Weight
3.1kg max
4.2kg max
*1 Only capacitor code and option “155”,“335”, Three Phase D-connection:400 (440 max), Wye-connection:500(528 max)
*2 Only option “U”, Three Phase 250(275 max)
*3 Only capacitor code and option “155”,“335”, 2,800VDC (Cutoff Current = 10mA), 1minute at room temperature and humidity.
*4 Only capacitor code and option “155”,“335”, Isolation resistance specification is deleted.
Circuit Diagram
(1) Line to ground capacitor code : 223, 683, 104
(2) Line to ground capacitor code : 155, 335
(3) Line to ground capacitor code : 223, 683, 104
Option : U
Case
LINE
Case
LINE
Case
LINE
LOAD
LOAD
LOAD
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
CY
CY
CY
CY
CY CY
CY : Line to ground capacitor
: Mounting Plate
CY : Line to ground capacitor
: Mounting Plate
CY : Line to ground capacitor
: Mounting Plate
(4) Line to ground capacitor code : 155, 335
Option : U
(5) Line to ground capacitor code : 155, 335
Option : G
Derating Curve
Case
LINE
Case
LINE
LOAD
LOAD
100
80
60
40
20
0
1
2
3
4
5
6
1
2
3
4
5
6
CY CY
CY CY
SW
-40
-30 -20
Ambient Temperature [C]
*Keep free ventilation holes for cooling.
40
50
60
70
80
90
CY : Line to ground capacitor
: Mounting Plate
SW : Switch
CY : Line to ground capacitor
: Mounting Plate
(The switch state is OFF)
FTA-7