MODEL: FJFX
(Minimum span 30 mV, Input resistance 20 kΩ min.)
Space-saving Plug-in Signal Conditioners F-UNIT
U3: Range ±10 V;
(Minimum span 0.3 V,Input resistance 1 MΩ min.)
LINEARIZER
(field-programmable)
[2] OUTPUT
Functions & Features
Current
• Accepting non-linear input and providing a linearized
output, proportional to the process variables
• Micro-processor based
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
6: 1 – 5 V DC (Load resistance 500 Ω min.)
• On-site calibration up to 16 points using a hand-held
programmer PU-2x
• Field-programmable input range
• High-density mounting
[3] POWER INPUT
AC Power
K: 85 – 132 V AC
Typical Applications
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
L: 170 – 264 V AC
• V-notch weir
• Gas analyzer
(Operational voltage range 170 – 264 V, 47 – 66 Hz)
DC Power
• Irregular-shaped tank level input for volume calculation
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
26 (1.02)
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
100
(3.94)
[4] OPTIONS
blank: none
/Q: With options (specify the specification)
137
(5.39)
mm (inch)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
MODEL: FJFX–[1][2]–[3][4]
/C02: Polyurethane coating
ORDERING INFORMATION
• Code number: FJFX-[1][2]-[3][4]
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
Specify a code from below for each of [1] through [4].
(e.g. FJFX-6A-L/Q)
• Special input range (For codes U1, U2 & U3)
• Linearization data (max. 16 points)
Use Ordering Information Sheet (No. ESU-1669) to specify
linearization data when the I/O signals are nonlinear.
• Specify the specification for option code /Q
(e.g. /C01/S01)
RELATED PRODUCTS
• Programming Unit (model: PU-2x)
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
[1] INPUT
Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
H: 10 – 50 mA DC (Input resistance 100 Ω)
Voltage
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
U1: Range ±100 mV;
(Minimum span 3 mV, Input resistance 20 kΩ min.)
U2: Range ±1000 mV;
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
FJFX SPECIFICATIONS
ES-1472 Rev.12 Page 1/4
http://www.m-system.co.jp/