HPF24S6 and
HPF24S8
Description
Power Supplies with Battery Chargers
The HPF24S6 and HPF24S8 are compact, cost-effective, 6
amp. or 8 amp. remote power supplies with integral battery
chargers. These adaptable power supplies may be con-
nected to any 12 or 24 volt Fire Alarm Control Panel
(FACP) or the power supplies may stand alone. Primary
applications include the following:
•
Notification Appliance Circuits (NAC) expansion to sup-
port ADA requirements and NAC synchronization
Auxiliary power to support 24 volt system accessories
•
HFP24S6/8
dh1061.jpg
These power supplies provide regulated and filtered 24
VDC power to four (4), notification appliance circuits, con-
figured as either four Class B (Style Y) or Class A (Style A,
with ZNAC-4 Option Module). Alternately, the four outputs
may be configured as follows:
Features
•
UL Listed NAC synchronization using System Sensor,
Cooper-Wheelock or Gentex (Commander Series)
appliances.
•
•
•
•
all non-resettable
all resettable
•
•
•
Cascade up to ten (10) power supplies (four (4) power
supplies with Gentex) with strobe timing maintained.
Operates as a sync follower or a sync generator
(default).
two non-resettable
two resettable
The power supplies also contain a battery charger with a
charging capacity of up to 18 Amp Hour batteries.
Contains two (2), fully -isolated input/control circuits
energized from FACP notification appliance circuit
(NAC expander mode) or jumpered permanently on
(stand-alone mode).
The HPF24S6 and HPF24S8 power supplies comply with
the following Agency standards:
•
•
NFPA 72 National Fire Alarm Code,
•
•
•
Configured to internally house addressable SLC control
module for alarm activation.
UL Standard 864, 9th Edition for control units for Fire
Alarm Systems (NAC expander mode).
UL 1481 Power Supplies for Fire Alarm Systems
(stand-alone mode).
Four (4) Class B (Style Y) or four (4), Class A (Style Z)
(with ZNAC-4 Module) notification appliance circuits.
6.0A or 8.0A (depending on model) full load output
(3.0A maximum per circuit) in NAC expander mode
(UL Standard 864).
•
•
4.0A or 6.0A continuous output in stand-alone mode
(UL Standard 1481).
An ISO 9000-2000 Company
SIGNALING
UOXX.S6677 7315-1637:102
UTRZ.S6677
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
©2007 Honeywell International Inc. All rights reserved.
Specifications are for information only, are not intended for installation pwurpwoswes,.ganadmareeswubejecllt-tofcchia.cngoemwithout notice. No responsibility is assumed by Gamewell-FCI for their use.
CS-60062 Rev. A1 page 1 of 2