DF-51401 D-100
July13, 2004
FCPS-24F(E)
24 Volt, 6 Amp Remote Power Supply
www.firelite.com
Section: Power Supplies/Accessories
California
State Fire
Marshal
7315-0075:176
(FCPS-24F)
GENERAL
The FireLite FCPS-24F(E) is a compact, cost-effective, 6-
amp remote power supply with battery charger. The FCPS-
24F(E) may be connected to any 12- or 24-volt Fire Alarm
Control Panel (FACP) or may stand alone. Primary appli-
cations include Notification Appliance (bell) Circuit (NAC)
expansion (to support ADA requirements) or auxiliary
power to support 24-volt system accessories. The FCPS
provides regulated and filtered 24 VDC power to four No-
tification Appliance Circuits (two Class A [Style Z] and two
Class B [Style Y] or four Class B only). Alternately, the four
outputs may be configured as any combination of reset-
table/non-resettable power outputs (optimal for powering
four-wire smoke detectors). The FCPS-24F(E) also con-
tains a battery charger capable of charging up to 7.0 Amp
Hour batteries.
CS868
(FCPS-24F)
S2424
S1287
(FCPS-24F
FCPS-24FE)
MEA
387-94-E
(FCPS-24F)
FEATURES
Requires input trigger voltage of 9.0 - 32 VDC.
Contains two, fully-isolated input/control circuits (trig-
gered from FACP Notification Appliance Circuit [NAC
expander mode] or jumpered permanently on [stand-
alone mode]).
Two Class A (Style Z) or Class B (Style Y) Notification
Appliance Circuits (circuits 1 & 3).
Two additional NACs that may be individually configured
for Class B (Style Y) operation only (circuits 2 & 4).
6 Amp full load output (3 amps max./ckt.) in NAC ex-
pander mode (UL 864).
4 Amp continuous output in stand-alone mode (UL 1481).
In stand-alone mode, output power circuits may be con-
figured as resettable (reset line from FACP required) or
non-resettable.
Fully regulated and filtered power output (optimal for
powering four-wire smoke detectors, annunciators and
other system peripherals requiring regulated/filtered
power).
Self-contained in compact, lockable cabinet (15" [381
mm] H x 14.5" [368 mm] W x 2.75" [70 mm] D).
Fuseless, power-limited technology meets new UL power-
limiting requirements, effective May 1, 1995.
Normally closed trouble contact.
Fully supervised power supply, battery and Notification
Appliance Circuits.
Includes integral battery charger capable of charging up
to 7.0 AH batteries.
Fixed, clamp-type terminal blocks accommodate up to 12
AWG (3.25 mm²) wire.
STANDARDS and CODES
Selectable earth fault detection.
AC trouble report selectable for immediate, 8 or 16 hour
delay.
The FCPS-24F complies with the following standards:
NFPA 72 National Fire Alarm Code.
Optional ammeter/voltmeter.
UL 864 Standard for Control Units for Fire Alarm Systems
(NAC expander mode).
UL 1481 Power Supplies for Fire Alarm Systems
(stand-alone mode).
Works with virtually any UL 864 fire alarm control which
utilizes an industry-standard reverse-polarity notification
circuit.
FireLite® Alarms is a Honeywell company.
This document is not intended to be used for installation purposes. We try to keep our product
information up-to-date and accurate. We cannot cover all specific applications or anticipate all
requirements. All specifications are subject to change without notice.
For more information, contact FireLite Alarms, One Fire-Lite Place, Northford, Connecticut 06472.
Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105.
DF-51401 07/13/04 Page 1 of 3