5秒后页面跳转
FBP-100 PDF预览

FBP-100

更新时间: 2024-02-28 23:27:35
品牌 Logo 应用领域
其他 - ETC 电路保护
页数 文件大小 规格书
3页 73K
描述
Fuse

FBP-100 技术参数

是否Rohs认证:不符合生命周期:Active
Reach Compliance Code:compliantECCN代码:EAR99
Factory Lead Time:3 weeks 6 days风险等级:5.51
Is Samacsys:N主体高度:54 mm
主体长度或直径:27 mm电路保护类型:ELECTRIC FUSE
安装特点:INLINE/HOLDER物理尺寸:27mm x 54mm
额定分断能力:200000 A额定电流:100 A
额定电压(交流):700 V额定电压(直流):700 V
参考标准:UL表面贴装:NO
端子形状:TAB/BLADEBase Number Matches:1

FBP-100 数据手册

 浏览型号FBP-100的Datasheet PDF文件第2页浏览型号FBP-100的Datasheet PDF文件第3页 
®
Bu s s m a n n  
S e m ic o n d u c t o r Fu s e s  
FBP  
7 0 0 Vo lt s AC/DC, 3 5 -1 0 0 0 Am p s  
Ultra High Degree of Current Limitation and Low I2t.  
• The heat energy of even low-level fault currents can quickly  
destroy a semiconductor device.  
* Buss FW type fuse limits peak let-thru current to a level  
which is a fraction of the potential available short-circuit peak  
current.  
• Fast speed-of-response to build-up of short-circuit current  
and the quickly decaying short-circuit current as the fuse  
suppresses internal arcing together can limit the I2t let-thru to  
values substantially lower than the I2t withstand of the semi-  
conductor device.  
Current Rating.  
• Current rating is given in AC (rms) for an ambient tempera-  
ture of 20ºC (68ºF).  
• Although these fuses can be operated at 100% of rating,  
good design practice dictates some derating (i.e. for ambient  
temperature), typically this is 20%.  
Voltage Rating.  
• Rated voltage of Semiconductor fuses is given in terms of  
A.C. operation, 60Hz.  
• When used in D.C. circuits no voltage derating is required  
provided the minimum interrupting capability is eight times  
the fuse rating and the time constant does not exceed those  
specified in U.L. 198L.  
Total Clearing I2t.  
CATALOG SYMBOL: FBP  
700V AC, 700V DC  
INTERRUPTING RATING 200,000 AMPERES  
RMS SYMMETRICAL  
• Maximum values of total clearing I2t are obtained at the rated  
A.C. voltage, an arcing angle between 60º and 90º, at an  
available symmetrical rms current of 100,000 amperes, and  
at a power factor of less than 15%.  
U.L. RECOGNIZED  
(GUIDE #JFHR2, FILE # E56412)  
Arc Voltage.  
• The arc voltage which develops across a fuse when it is  
clearing a fault current must always exceed the system volt-  
age.  
Catalog Numbers  
FBP-35  
FBP-40  
FBP-50  
FBP-60  
FBP-70  
FBP-80  
FBP-350  
FBP-400  
FBP-450  
FBP-500  
FBP-600  
FBP-700  
FBP-800  
FBP-900  
FBP-1000  
• This arc voltage may reach a value which is twice that of the  
system applied voltage.  
FBP-90  
FBP-100  
FBP-125  
FBP-150  
FBP-175  
FBP-200  
FBP-250  
FBP-300  
Form No. FBP  
Page 1 of 3  
BIF Doc #720041  
12-17-98  
SB98107  
Rev. A