COMMANDER CLASS - CHASSIS MOUNT WITH LEAD WIRES POWER TRANSFORMER
1. Electrical Specifications
A. Maximum Power: 12VA
Standard 6” Lead Length
B. Input Voltage and Frequency: 115V, 115/230V or 230V
50/60Hz
C. Voltage Regulation: 18% TYP @ full load to no load
D. Temperature Rise: 30C TYP
E. Insulation Resistance: < 1 MEG ohm
F. Hi-Pot: 2500Vrms 1 minute @ Pri to Sec
2500Vrms 1 minute @ Pri to Core
1500Vrms 1 minute @ Sec to Core
2. Marking: Ensign Corp, part number (see table), date code
3. Safety:
UL/cUL 5085-2 Recognized (File E47299)
UL 1446 Recognized Insulation System (File E95662)
Part Number
115V
115/230V
230V
Secondary
L012-1-510X
L012-1-512X
L012-1-516X
L012-1-520X
L012-1-524X
L012-1-528X
L012-1-536X
L012-1-548X
L012-1-556X
L012-1-620X
L012-2-510X
L012-2-512X
L012-2-516X
L012-2-520X
L012-2-524X
L012-2-528X
L012-2-536X
L012-2-548X
L012-2-556X
L012-2-620X
L012-3-510X
L012-3-512X
L012-3-516X
L012-3-520X
L012-3-524X
L012-3-528X
L012-3-536X
L012-3-548X
L012-3-556X
L012-3-620X
10VCT @ 1.2A
12.6VCT @ 1.0A
16VCT @ 800mA
20VCT @ 600mA
24VCT @ 500mA
28VCT @ 420mA
36VCT @ 350mA
48VCT @ 250mA
56VCT @ 220mA
120VCT @ 100mA
Primary Schematics
Single Input
(Specify 115V
or 120V
Single Input
Single Input
(277V)
Dual Input
Tapped Input
WHT=COM
BLK=120
(Specify 230V
or 240V)
(Specify
115/230V or
120/240V)
VIO=277V
Secondary Schematics
L012-1-XXXX
L012-2-XXXX
L012-3-XXXX
POWER TRANSFORMER
COMMANDER CLASS
CONTENTS OF THIS DRAWING ARE SUBJECT TO
CHANGE WITHOUT PRIOR NOTICE
Dim: Inches
Sheet 1 of 1
Ensign Corporation
201 ENSIGN RD., BELLEVUE, IA 52031
Single
Output
Center-Tapped
Dual
Output
Output
PROPRIETARY NOTICE: THIS DRAWING PRINT OR DOCUMENT AND SUBJECT MATTER DISCLOSED HEREIN ARE PROPRIETARY ITEMS TO WHICH ENSIGN RETAINS
THE EXCLUSIVE RIGHT OF DISSEMINATION, MANUFACTURE AND SALE. THIS DRAWING, PRINT OR DOCUMENT IS SUBMITTED IN CONFIDENCE FOR CONSIDERATION
BY THE RECIPIENT ALONE UNLESS PERMISSION FOR FURTHER DISCLOSURE IS EXPRESSLY GRANTED IN WRITING