Ordering information
Small, Single phase input type (1-Stage filter)
EAC -10 -472 -O
EAC/EAM/EAP series
1
2
3
4
1Series Name
2Rated Current
R
3
Line to ground capacitor code: Refer to table 1.1.
table1.1 Line to ground capacitor code
EAECAEMAP
Line to ground
Leakage Current
(Input 125/250V 60Hz)
Code
capacitor
(nominal value)
000
101
221
331
● ●
● ● 12.5 A / 25 A max
● ● 25
A / 50 A max
● ● 37.5 A / 75 A max
● ● 50
A / 100 A max
● 75.5 A / 150 A max
●
●
●
●
5
A / 10 A max Not Provided
100pF
220pF
330pF
470pF
680pF
471
681 ●
102 ●
222 ●
332 ●
472 ●
0.13mA / 0.25mA max 1,000pF
0.25mA / 0.5 mA max 2,200pF
0.38mA / 0.75mA max 3,300pF
0.5 mA / 1.0 mA max 4,700pF
When the line to ground capacitor code is
different, the attenuation characteristic is
different.
*
4Option
D:DIN rail installation type
The terminal cover is retracted inside the unit
DIN rail installation type is option
The dimensions change when the option is set.
Refer to External view.
*
Features of EAC/EAM/EAP series
Single Phase 250VAC (1-Stage filter)
Small size
-
-
Quick and easy push-down terminal
-ꢀ
Just connect the wires, push-down and tighten the screws with a screwdriver
EAC: Attenuation type from 150kHz to 1MHz
EAP: Outside impulse attenuation type
EAM : Low leakage current type
Specifications
EAC-03-472
EAM-03-000
EAP-03-472
EAC-06-472
EAM-06-000
EAP-06-472
EAC-10-472
EAM-10-000
EAP-10-472
EAC-16-472
EAM-16-000
EAP-16-472
EAC-20-472
EAM-20-000
EAP-20-472
EAC-30-472
EAM-30-000
EAP-30-472
No.
Items
1
2
Rated Voltage[V]
Rated Current[A]
AC 1f250 / DC250
3
6
10
16
20
30
3
Test Voltage (Terminal-Mounting Plate)
2,500 VAC (Cutoff Current = 20mA), 1minute at room temperature and humidity
4
Isolation Resistance (Terminal-Mounting Plate) 500 VDC 500MWmin at room temperature and humidity
5
6
Leakage current
DC resistance
Refer to table 1.1
180mWmax 110mWmax
40mWmax
20mWmax
10mWmax
6mWmax
7
8
9
Safety agency approval temperatures
Operating temperature
Operating humidity
-25 to +85C(Refer to Derating Curve)
-40 to +85C(Refer to Derating Curve)
20 to 95%RH (Non condensing)
10
11
12
13
14
Storage temperature/humidity
Vibration
Impact
Safety agency approvals
Case size (without projection) /Weight
-40 to +85C/20 to 95%RH (Non condensing)
2
10 to 55Hz, 19.6m/s (2G), 3min. Period, 1hour each X, Y and Z axis
2
196.1m/s (20G), 11ms Once each X, Y and Z axis
UL1283, CSA C22.2 No.8 (C-UL), DIN EN60939 VDE0565 Teil3-1, ENEC (At only AC input)
39X30X85 mm [1.54X1.18X3.35 inches] (WXHXD) /170g max (Option : -D refer to external view)
Circuit Diagram
Derating Curve
Case
100
80
3
1
60
CY
CY
LINE
LOAD
40
4
2
20
0
-40
-30
-20
40
50 55 60
70
80
90
Ambient Temperature [C]
: Mounting Plate
CY : Line to ground capacitor
May 11, 2021
EA/ES-1