DIESEL GENERATOR SET
DS250D6S
/
/
250 kWe 60 Hz Standby
208 - 600V
(Reference DP230D6S for Prime Rating Technical Data)
SYSTEM RATINGS
Standby
DS250D6SPA
DS250D6SJA
DS250D6SVA
DS250D6SWA
DS250D6SRA
DS250D6SNA
Voltage (L-L)
Phase
208V**
3
240V**
3
380V
3
440V
3
480V**
3
600V**
3
PF
Hz
0.8
60
0.8
60
0.8
60
0.8
60
0.8
60
0.8
60
kW
kVA
Amps
250
312
867
250
312
752
250
312
475
250
312
410
250
312
376
250
312
301
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
608
608
430
580
809
720
432CSL6210
130 °C/40 °C
12 LEAD LOW WYE
432CSL6210
130 °C/40 °C
12 LEAD HI DELTA
432CSL6210
130 °C/40 °C
12 LEAD HI WYE
432CSL6210
130 °C/40 °C
12 LEAD HI WYE
432CSL6210
130 °C/40 °C
12 LEAD HI WYE
432PSL6246
130 °C/40 °C
6 LEAD WYE
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
//ꢀ
//ꢀ
Emissions – EPA Tier 3 Certified
Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
//ꢀ
Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
- Verified product design, quality and performance integrity
ISO 14001:2004
- All engine systems are prototype and factory tested
//ꢀ
//ꢀ
UL 2200 / CSA – Optional
Power Rating
– UL 2200 Listed
– CSA Certified
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 85%.