DRC Series
1 0 - 1 0 0 W AT T S A C / D C D I N R A I L
FEATURES
• 10W - 100W
• DIN rail mountable
• Protection Class II
• Double Isolation (No earth connection required)
• Universal AC input voltage and full power up to 55°C
• Efficiency > 89.0% 230VAC
• NEC Class 2/Limited Power Source (LPS) certified
• Overvoltage/Overcurrent/Over Temperature Protections
• International safety approvals to ITE and Industrial standard
SPECIFICATIONS
OUTPUT
MECHANICAL
Output Voltage
5V, 12V, 24V
Case Cover
Plastic
5Vdc, 4.75V - 5.25Vdc
12Vdc, 11.5V - 14.5Vdc
24Vdc, 20V - 24.8Vdc
DRC 10W: 91 x 18 x 55.6mm, 0.065kg
DRC 30W: 91 x 53 x 55.6mm, 0.14kg
DRC 60W: 91 x 71 x 55.6mm, 0.24kg
DRC 100W: 91 x 89.9 x 55.6mm, 0.35kg
Voltage Range
Dimensions / Weight
Output Current
Output Power
Line Regulation
Load Regulation
PARD (20MHz)
Rise Time
See Selection Table
Indicator
Green LED (DC OK)
10W, 30W, 60W, 100W
Cooling System
Input Terminal
Output Terminal
Convection
< 1% typ. (@ 90-264 Vac,100% load)
< 2% typ. (@ 90-264 Vac,100% load)
< 150mVpp
2 Pins Rated 300V/25A (DRC10W 16A)
4 Pins Rated 300V/25A (DRC10W 16A)
DRC 10W: AWG 26-12
DRC 30W: AWG 24-12
DRC 60W: AWG 26-12
DRC 100W: AWG 22-12, AWG 24-12
< 100ms @ nominal input (100% load)
< 3,000ms @ nominal input (100% load)
>30ms @ 230Vac (100% load)
5% @ 10 - 100% load
Input / Output Wire
Start-up Time
Hold-up Time
Dynamic Response
Start-up
Mounting Rail
TS35 DIN Rail in accordance with EN 60715
3,000µF Max with Capacitive Loads
STANDARDS AND APPROVALS
C-Tick
INPUT
AS/NZS CISPR11 Group 1 Class A.
Input Voltage
Input Frequency
Efficiency
90-264Vac
TUV Bauart to EN60950-1, UL/cUL recognized to
UL60950-1, CSA C22.2 No. 60950-1, CB scheme
to IEC 60950 - 1, Limited Power Source (LPS)
47-63Hz
Safety
> 82% @ 230Vac at 100% load
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-
01
DRC 10W: < 0.2A @230Vac
DRC 30W: < 0.60A @230Vac
DRC 60W: < 0.80A @230Vac
DRC 100W: < 1.0A @ 230Vac
Industrial Control
Input Current
In conformance with EMC Directive 2004/108/EC
and Low Voltage Directive 2006/95/EC
CE
Leakage Current
PROTECTIONS
Overvoltage
< 0.25mA @ 240Vac
Materials and Parts
RoHS Directive 2011/65/EU Compliant
CISPR 22, EN55022, FCC Title 47: Class A* IEC
61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC
61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC
61000-4-11, IEC 61000-4-12
17.4V & 34.8V+10% SELV Ouput,Latch-off Mode
EMC
> 130% of rated load current, Hiccup Mode, Non-
Latching (Auto-Recovery)
Overload/Overcurrent
Over Temperature
> 75C Surrounding Air Temperature @ 100% load,
Latch-off Mode
Hiccup Mode, Non-Latching (Auto-Recovery) when
the fault is removed)
Short Circuit
Degree of Protection
IP20
Protection against Shock Class 1 with Primary Earth connection
Galvanic Isolation
MTBF
3.0KVac
> 500,000 hrs as per Telcordia SR-332
Doc. No. DRC Series Rev.C 15-9-15