20A Power Supply Redundancy Module
DR-RDN20
Features :
Suitable for redundant operation of 24V system
Installed on DIN Rail TS35 / 7.5 or 15
Relay contact signal output and LED indicator for input failure alarm
Cooling by free air convection
3 years warranty
SPECIFICATION
MODEL
DR-RDN20
REVERSE VOLTAGE (max.) 30V
OUTPUT CURRENT (max.)
20A
OUTPUT
VOLTAGE DROP
0.5V
LED INDICATORS
Two green LEDs indicating each input is "OK or fail"
INPUT VOLTAGE RANGE
NUMBER OF INPUTS
INPUT CURRENT (max.)
INPUT VOLTAGE ALARM
21 ~ 28V
Two
INPUT
20A per input
When input is > 20V( 5%) or < 30V( 5%) relay contacts
FUNCTION
RELAY CONTACT RATING (max.) 30VDC, 1A
WORKING TEMP.
-20 ~ +70
WORKING HUMIDITY
20 ~ 90% RH non condensing
ENVIRONMENT
STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mouning: Compliance to IEC60068-2-6
Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal :0.5KVAC
Terminal-Chassis :>100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, heavy industry level, criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
SAFETY &
EMC
(Note 2)
EMC IMMUNITY
MTBF
996.8Khrs min. MIL-HDBK-217F (25
55.5*125.2*100mm (W*H*D)
)
OTHERS
NOTE
DIMENSION
0.5Kg; 20pcs/11Kg/1.29CUFT
PACKING
1. All parameters NOT specially mentioned are measured at 24VDC input, rated load and 25 of ambient temperature.
2. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
Typical Application Notes
1. 1+1 Redundancy
2. 1+N Redundancy: Using more PSUs as the redundant units to increase the reliability
Using 1 more PSU as the redundant unit
PSU
PSU
PSU
PSU
PSU
PSU
PSU
PSU
..............
Vin A
Vin B
DR-RDN20
Vin A
Vin B
Vin A
Vin B
DR-RDN20
DR-RDN20
DR-RDN20
Vout
Load
Vout
Vout
Vout
Load
3. Single Use: Connecting only one PSU to one DR-RDN20 to reduce the stress of the diodes and hence increase the reliability
PSU
PSU
Vin A
Vin B
Vin A
Vin B
DR-RDN20
DR-RDN20
Vout
Vout
Load
File Name:DR-RDN20-SPEC 2011-06-17