45W Single Output Industrial DIN Rail Power Supply
DR-45 series
Features :
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fix switching frequency at 100KHz
3 years warranty
SPECIFICATION
MODEL
DR-4505
DR-4512
DR-4515
DR-4524
DC VOLTAGE
5V
12V
15V
24V
RATED CURRENT
CURRENT RANGE
RATED POWER
5A
3.5A
2.8A
2A
0 ~ 5A
25W
0 ~3. 5A
42W
0 ~ 2.8A
42W
0 ~ 2A
48W
RIPPLE & NOISE (max.) Note.2 100mVp-p
VOLTAGE ADJ. RANGE 4.75 ~ 5.5V
VOLTAGE TOLERANCE Note.3 2.0%
200mVp-p
10.8 ~ 13.2V
1.0%
240mVp-p
13.5 ~ 16.5V
1.0%
480mVp-p
21.6 ~ 26.4V
1.0%
OUTPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
800ms, 60ms/230VAC at full load
100ms/230VAC at full load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
85 ~ 264VAC
47 ~ 63Hz
72%
120 ~ 370VDC
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
77%
77%
80%
INPUT
1.5A/115VAC
0.75A/230VAC
COLD START 28A/115VAC
<1mA / 240VAC
56A/230VAC
105 ~ 150% rated output power
OVERLOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
5.75 ~ 6.75V 13.8 ~ 16.2V 17.25 ~ 20.25V
27.6 ~ 32.4V
PROTECTION
OVER VOLTAGE
OVER TEMPERATURE
Protection type : Shut off o/p voltage, clamping by zener diode
Tj 135 typically (U1) detect on heat sink of power transistor
Protection type : Shut down o/p voltage, re-power on to recover
-10 ~ +50 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
-20 ~ +85 , 10 ~ 95% RH
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
SAFETY &
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
Compliance to EN55011,EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
EMC
EMI CONDUCTION & RADIATION
(Note 4)
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
364.6K hrs min. MIL-HDBK-217F (25
93*78*67mm (L*W*H)
)
OTHERS
NOTE
DIMENSION
PACKING
0.31Kg; 48pcs/16.1Kg/1.3CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:DR-45-SPEC 2008-04-07