TOTAL POWER INT'L
45W Single Output Industrial DIN Rail Power Supply
DR-45 series
Features :
Universal AC input/Full range
Protections:Short circuit/Over load/Over voltage/Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fix switching frequency at 100KHz
3 years warranty
R
SPECIFICATION
MODEL
DR-4505
DR-4512
DR-4515
DR-4524
DC VOLTAGE
5V
12V
15V
24V
RATED CURRENT
CURRENT RANGE
RATED POWER
5A
3.5A
2.8A
2A
0 ~ 5A
25W
0 ~3. 5A
42W
0 ~ 2.8A
42W
0 ~ 2A
48W
100mVp-p
4.75 ~ 5.5V
2.0%
200mVp-p
10.8 ~ 13.2V
1.0%
240mVp-p
13.5 ~ 16.5V
1.0%
480mVp-p
21.6 ~ 26.4V
1.0%
RIPPLE & NOISE (max.) Note.2
VOLTAGE ADJ. RANGE
OUTPUT
VOLTAGE TOLERANCE Note.3
LINE REGULATION
1.0%
1.0%
1.0%
1.0%
LOAD REGULATION
1.0%
1.0%
1.0%
1.0%
SETUP, RISE, HOLD TIME
800ms, 60ms, 50ms/230VAC at full load
VOLTAGE RANGE
85 ~ 264VAC
47~63Hz
120 ~ 370VDC
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT
72%
77%
0.75A/230VAC
77%
80%
INPUT
1.5A/115VAC
INRUSH CURRENT (max.)
LEAKAGE CURRENT
COLD START 30A/115VAC
<1mA / 240VAC
60A/230VAC
105 ~ 150% rated output power
OVER LOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
5.75 ~ 6.75V 13.8 ~ 16.2V 17.25 ~ 20.25V
Shut down o/p voltage, re-power on to recover
Tj 135 typically (U1) Detect on heat sink of power transistor
27.6 ~ 32.4V
PROTECTION
OVER VOLTAGE
OVER TEMPERATURE
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-10 ~ +50 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
ENVIRONMENT
-20 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
VIBRATION
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
UL508, TUV EN60950 Approved
SAFETY STANDARDS
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
SAFETY &
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
Compliance to EN55011,EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
EMC
(Note 4)
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A
MTBF
364.6K hrs min. MIL-HDBK-217F (25
93*78*67mm (L*W*H)
)
OTHERS
NOTE
DIMENSION
0.31Kg; 48pcs/14.8Kg/1.3CUFT
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.