• Low Cost
• 12, 24 or 48V Outputs
• Wide Range AC Input
• Parallel Function Switch
• -25 to +71°C Operation
Key Market Segments & Applications
Industrial Controls:
Factory Automation:
Motor Control Systems
Process Control, Automotive,
Chemical Processing
Burn in & Test,
Instrumentation Measurement
DPP120 & 240 Series
Test & Measurement:
120W & 240W Single Output
DIN Rail Mount Power Supplies
DPP120 & 240 Features and Benefits
Features
Benefits
• PFC Compliant to EN61000-3-2
• UL508 Approvals
• Supports Global Use
• Easier System Configuration
• Easy System Integration
• TS35/7.5 or TS35/15 DIN Rail Mounting
Specifications
MODELS
DPP120
DPP240
ITEMS
AC Input Voltage range
Input Frequency
DC Input Voltage range
Inrush Current (115 / 230VAC)
Power Factor
VAC
Hz
VDC
A
90 - 132/186-264VAC (auto select)
47 - 63Hz
210 - 370VDC
24/48A
30/60A
-
typ 0.7 at 230VAC input
Input Current (115/230VAC)
Output Voltage
Output Voltage Accuracy
Line Regulation
A
V
%
%
%
mV
-
2.8/1.4A
12 , 24 or 48V
5.4/2.2A
24 or 48V
-0, +1% of Nominal
0.5%
Load Regulation
+1% Single Mode
<50mV
+5% Parallel Mode
<100mV
Ripple and Noise (20MHz BW)
Overcurrent Protection (Typ)
Overvoltage Protection
Hold Up Time (230VAC input)
Efficiency (typ)
120 - 145%
120 - 145%
>30 ms
V
ms
%
-
84 - 90% (see table)
Up to 3 units
Parallel operation
LED Indicators
-
Green LED = On, Red LED = DC Output Low
-0.3A rated normally open relay contacts, closes when output is above 17.6 - 19.4V
-25 to +71°C (Derate linearly 2.5% per °C from 61 to 71°C)
-25 to +85°C
DC Good Relay (24V model only)
Operating Temperature
Storage Temperature
Operating Humidity
Cooling
-
-
-
-
20 - 95% RH (non condendsing)
Convection
Withstand Voltage
-
-
-
-
g
Input to Output 3kVAC for 1 min.
Isolation Resistance
Safety Agency Approvals
Conducted & Radiated EMI
Weight (Typ)
>100M at 25C & 70%RH, Output to Ground 500VDC
UL508 Listed, UL60950-1, EN60950-1, CE
EN55022 class B
920
1000
Size (HxWxD)
Case material
mm
-
125 x 63.5 x 123.6
125 x 83 x 126
Metal
Warranty
yrs
Two years
1
DPP120 & 240 Series