AC/DC Current Transducer DHR-C5
The transducer for the electronic measurement of DC & distorted AC
waveform currents, with galvanic isolation between the primary circuit
(power) and the secondary circuit (measurement). True RMS 0-5V
voltage output.
IPN = 100 .. 400 A
Electrical data
Primary Nominal Primary AC Current
DC & AC Current
Output voltage
(Analog)
VOUT (VDC)
0-5
Type
Max. Peak Value1)
Features
I
PN (A.t.RMS)
100
IP (A)
600
DHR 100 C5
DHR 200 C5
DHR 300 C5
DHR 400 C5
● VFD and SCR waveforms current
measurement
● True RMS output
200
600
0-5
0-5
0-5
300
400
1000
1000
● Panel mounting
● Eliminates insertion loss
● Isolated plastic case recognized
according to UL94-V0
RL
VC
IC
VSL
ÎP
Load resistance
≥ 10
+ 20 .. 50
30
< 7
30000
kW
V DC
mA
V
Supply voltage2)
Current consumption
Output voltage limitation (0 - 5 V)
Overload capability (Ampere Turns)
Advantages
A.t
● Large aperture for cable up to
Ø32mm
Performance data
● High isolation between primary
and secondary circuits
● Easy installation
X
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (1% of IPN .. ± IPN)
Electrical offset voltage, TA = 25°C
< ± 1
% of IPN
% of IPN
% of IPN
mV/K
mV/K
%/K
e
< ± 1.0
< ± 1.0
± 2.0
± 4.0
± 0.1
L
Applications
VOE
TCVOE Temperature coefficient of VOE ( 0..+60 °C)
(-40..+70 °C)
TCVOUT Temperature coefficient of VOUT (% of reading)
● VFD Controlled Loads
VFD output indicates how the
motor and attached load are
operating.
● SCR Controlled Loads
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs. Current
measurement gives faster
response than temperature
measurement.
tr
Response time to 90 % of IPN step
< 150
DC 20..6000
ms
Hz
BW
Frequency bandwidth (± 1 dB)
General data
TA
TS
m
Surrounding operating temperature
Surrounding storage temperature
Mass
- 40 .. + 70
- 40 .. + 85
260
°C
°C
g
IPxx Protection degree
IP20
● Switching Power Supplies and
Electronic Ballasts
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Notes :1) The Max. Peak AC Current is the highest peak level of the primary
signal that is taken into account for accurate True RMS calculation. Yet
the device is designed for maximum continuous True RMS value equal to
IPN, whereas the output is limited by the above specified output limitation.
2) According to the UL 508 Standard for Safety for Industrial Control
Equipment, the supply voltage must not exceed 42VDC.
Application domain
● Energy and Automation