Current Transducer CT 50-T
IPN = 50 A
For very accurate measurements of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Preliminary
Electrical data
IPN
IP
Primary nominal r.m.s. current
Primary current, measuring range
50
0 .. ± 75
5
50 A / 5 V
> 500
£ 5
A
A
V
Features
VOUT Analog output voltage
· Closed loop (compensated) current
transducer
· Insulated plastic case recognized
according to UL 94-V0
KN
RL
CL
tC
VC
IC
Conversion ratio
Load resistance
Capacitance loading
Output short-circuit duration 1)
Supply voltage (± 5 %)
W
nF
s
¥
± 15
· Patent pending.
V
Current consumption
90 + VOUT /RL mA
Advanced features
Vd
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
6
kV
· f = 500 kHz
· XG = ± 0.1 % (- 25°C .. + 70°C).
Accuracy - Dynamic performance data
Advantages
XG
VO
f
Overall accuracy @ IPN
Offset voltage @ IP = 0
- 25°C .. + 70°C
± 0.1
Typ
%
· Excellent accuracy
· Very good linearity
Max
TA = 25°C
- 25°C .. + 70°C
± 0.4 mV
± 0.6 mV
· Low temperature drift
· Optimized response time
· Wide frequency bandwidth
· No insertion losses
· High immunity to external
interference
Frequency bandwidth (- 3 dB) @ 10 % of I PN
DC .. 500
kHz
General data
· Current overload capability.
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
- 25 .. + 70
- 40 .. + 85
670
°C
°C
g
Applications
· AC variable speed drives and servo
motor drives
2)
Standards
EN 50178
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptible Power Supplies
(UPS)
· Switched Mode Power Supplies
(SMPS)
· Power supplies for welding
applications.
1)
Notes : If the short-circuit has a duration more than 1 s, the primary current of
the supply voltage must be interrupted for a short time to restore the
transducer to proper working order. The internal protection is done by
PTC resistors
2)
980814/5
A list of corresponding tests is available
LEM Components
www.lem.com