Features  
CIM-8  
Eight circuit modules.  
• Compatible with IF632 and IF650  
systems.  
Conventional Input Module  
• Module removal without disturbing field  
wiring.  
• LED annunciation of alarm and trouble per  
zone.  
• Tactile switch per zone for programming  
and bypass.  
• Style B, C, D, and E wiring.  
• Requires one bus position in the IF632 or  
IF650.  
• Alarm verification per zone.  
• Supervisory service.  
• Compatible with two- or four-wire  
devices.  
• Distinguishes between contact devices  
and conventional smoke detectors.  
Description  
Available in eight-zone increments, the Conventional Input Module (CIM)  
monitors conventional type devices such as smoke detectors, heat detectors,  
manual stations, and other contact type devices connected to Gamewells  
IF632 and IF650 Fire Alarm Control Panels (FACPs). The CIM can be  
programmed to provide remote signal silence, acknowledge, reset, and drill  
service. Each module has a display module providing LED annunciation of  
alarms and troubles. The display module allows custom labeling of each  
circuit. Each zone has a switch on the display module for programming of  
zone functions, zone bypass, and walk test.  
Specifications  
Refer to installation instructions for  
maximum allowable two-wire detectors  
per zone.  
Standby current  
100 mA (8-circuit CIM).  
Alarm current  
86 mA per active circuit.  
Standard Applications  
The CIM monitors nonaddressable inputs to the IF632 and IF650 Fire  
Alarm Panels. Each circuit can be individually programmed for Fire Alarm,  
Security Alarm, Supervisory Alarm, Remote Reset, Acknowledge, Signal  
Silence, or Drill. Zones can also distinguish between contact type devices  
and a smoke detector in alarm, enhancing the alarm verification capabili-  
ties on each circuit.  
Listings  
Listings and approvals below apply to the  
Conventional Input Module. In some  
cases, certain modules may not be listed  
by certain approval agencies, or listing  
may be in process. Consult factory for  
latest listing status.  
Operation  
• UL Listed: file S521.  
The CIM monitors each circuits current; the main CPU then interrogates  
the CIM for the data returned from each circuit. If the CPU detects an off-  
normal reading, the system executes its programmed response.  
• CSFM approved: files 7165-1288:144,  
7165-1288:146.  
• MEA approved: file 132-95-E.  
• FM approved.  
If the CPU receives a trouble response back from the module, the system  
will initiate the appropriate trouble sequence. If the response from the  
module indicates a device in alarm, the CPU will identify the type of device  
and will initiate the pre-programmed alarm sequence.  
CIM-8 CS-2026 09/01/06  
Page 1 of 2  

与CIM-8相关器件

型号 品牌 获取价格 描述 数据表
CIM-86S7B CITIZEN

获取价格

Infrared IrDA Compliant Transceiver
CIM-9 LUMINUS

获取价格

COB Arrays White LED
CIM-9-24-90-18-AC40-F5-2 LUMINUS

获取价格

COB Arrays White LED
CIM-9-24-90-18-AC40-F5-3 LUMINUS

获取价格

COB Arrays White LED
CIM-9-24-90-36-AC40-F5-2 LUMINUS

获取价格

COB Arrays White LED
CIM-9-24-90-36-AC40-F5-3 LUMINUS

获取价格

COB Arrays White LED
CIM-9-27-80-18-AC40-F5-2 LUMINUS

获取价格

COB Arrays White LED
CIM-9-27-80-18-AC40-F5-3 LUMINUS

获取价格

COB Arrays White LED
CIM-9-27-80-36-AC40-F5-2 LUMINUS

获取价格

COB Arrays White LED
CIM-9-27-80-36-AC40-F5-3 LUMINUS

获取价格

COB Arrays White LED