Catalog: 1654986
Issue Date: 11.2009
Corcom Facility EMI Filters Product Guide
CDEUX Series - Extended Range Buffer Networks (Capacitive Input)
CDEUX Series
Filter Cabinet
• Modified NEMA I, constructed of not less than #14
gauge CRS with galvanized bulkhead
6P16 †
• Blue epoxy finish to all non-conductive surfaces
• R.F. Radiation of the shielded (load) compartment
greater than 100 dB from 14 kHz to 10 GHz
• Front cover access, dual cover design
• Filter inserts pre-wired to standoffs and lugs
• Lifting hooks and mounting tabs
• Legs for floor mount available (see page 24)
Individual Filters
• Sealed components with welded and/or soldered
seams
• Constructed of not less than #16 gauge steel with
corrosion resistant plating
• Bleeder resistor to eliminate shock hazard provided
• Surge arrestors provided upon request‡
Electrical Characteristics
Voltage Drop:
Less than 1% @ unity power factor
Overload:
140% of rated current for 15 minutes
Harmonic Distortion:
Less than 2% @ full rated current
Dielectric Withstanding Voltage:
Per MIL-PRF-15733 and UL1283
D.C. Insulation Resistance:
Per MIL-STD-202, Method 302
Terminal Strength:
Per MIL-STD-202, Method 211, Condition E
Temperature Rise:
Shown with optional legs
Per MIL-PRF-15733 and UL1283
How to Order:
R.F. Radiation:
CDEUX 4 01000 A6 -S -L
100 dB minimum shielding effectiveness
Legs
1
Surge Arrestors (optional)
Insertion Loss:
Voltage/Frequency
A6 - 120/208V, 60Hz
B6 - 277/480V, 60Hz
A4 - 120/208V, 400Hz
Current Rating 2
# of Filters
Series
100 dB from 14 kHz - 10 GHz per MIL-STD-220A, under
load condition, using extended range buffer networks
over the frequency range of 14 kHz - 20 MHz
Applicable Publications:
Examples:
MIL-PRF-15733 — Filters, radio interference
MIL-STD-202 — Test methods for Components
MIL-STD-220A — Test method of Insertion Loss
MIL-STD-285 — Test method for Shielding Effectiveness
NFPA 70-1987 — National Electric Code
CDEUX401000A6-S-L =
4, 1000A CDEUX, 120/280V filters in cabinet
with surge arrestors and legs
CDEUX300030B6 =
3, 30A CDEUX, 277/480V filters in cabinet
486A - 1983 — Wire Connectors and Lug
UL1283 — Underwriter Laboratories
Note 1:
Note 2:
Surge Arrestor for A6/A4* Models: V251BA60
Surge Arrestor for B6 Models: V481BA60
Current configuration listed as 5 digits with leading zeros
‡ Not intended for HEMP applications. Refer to the CDEUL(<150A)
page 12 or TECUL Series (>225A) page 14 for HEMP applications..
† 60 Hz Models Only
10
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric
equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
USA Cust. Svc.:
Corcom Prods:
1-800-468-2023
1-847-680-7400
www.tycoelectronics.com
www.corcom.com