600 Series
IdentiFlex 610
with SmartScan™
Analog Addressable Control Panel
Description
The IdentiFlex 610 (IF610SS) with SmartScan™ is suited
for medium-sized installations of commercial, institutional,
and industrial life-safety applications.
The IF610SS offers all the features of today’s most
advanced life safety systems. The integration of analog
and addressable hardwired circuits allows system engi-
neers to customize panels and maximize efficiency for a
given application. The IF610SS can be networked with up
to 256 other 600 Series panels using Gamewell-FCI’s
SmartLink™ peer-to-peer network.
IF610SS
Features
The IF610SS can monitor and control up to 792 intelligent
analog addressable input/output points. Analog circuits are
backed up by Gamewell-FCI’s Default Alarm Mode for
added security. The 1,000-point history log furnishes a
complete record of system activities. The interactive opera-
tor’s display uses LED prompting for ease of programming
and user operation. The alphanumeric display and keypad
simplify field programming, or program from a PC using
Gamewell-FCI’s SmartProgram II programmer.
•
•
Two or four Signaling Line Circuits (SLC), up to 792
points.
SmartScan™ protocol — up to 99 detectors and 99
devices per loop.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
SmartStart™ self-programming logic.
Programmable by PC or front panel.
Password protected.
Approved for Supervisory Service.
Fully digital SLC protocol.
SmartLink™ networkable.
1000-event history log.
Automatic drift compensation.
Coded signaling capability.
Adjustable sensor sensitivity and temperature settings.
Day/night sensitivity setting.
The IF610SS’s cabinet will fit between 16" studs for semi-
flush mounting. The compact design and key-activated
dead-front construction enables secure routine mainte-
nance of the system. Access to system function keys is lim-
ited by a key switch. Multiple levels of password protection
prevent unauthorized use. The circuit boards are mounted
on a removable chassis, and are designed with pluggable
terminal strips for ease of installation and service.
Supervisory service.
Style 6 (Class A) or Style 4 (Class B) SLC.
Two Style Y (Class B), or two Style Z (Class A) notifica-
tion appliance circuits (NACs).
Semi-flush mounting (between 16" studs).
160-character display.
Optional integrated voice evacuation.
Optional UDACT.
Agent Releasing service.
Operator’s Display
The IF610SS’s operator’s display provides all user access
to the system. The display has all the necessary keys and
annunciation points to maintain and monitor the system.
Alarm, supervisory, and trouble conditions are indicated on
the operator’s display by dedicated LEDs and an internal
sounder. The Acknowledge, Reset, and Signal Silence
keys are located directly below the 4-line by 40-character
backlit alphanumeric display. All system functions and
operational logic can be programmed directly from the front
panel.
•
•
•
•
•
An ISO 9000-2000 Company
SIGNALING
SmartScan™ Series and SmartStart™ are trademarks of Honeywell International Inc.
Microsoft® Windows® is a registered trademark of Microsoft® Corporation.
FM
APPROVED
S521
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
©2007 Honeywell International Inc. All rights reserved.
Specifications are for information only, are not intended for installatiown pwurpwos.egs,aamndearwe seulblje-cftctoi.cchoanmge without notice. No responsibility is assumCeSd-b2y4G9a1meRweellv-F.CAI fopr athgeier u1se.of 3