Rack & Cabinet Mounting Converters
C
SERIES
150-12 k Watts
CE Marked - LVD & EMC
•
Over 1700 Different Models
•
DC Inputs 10 - 900 Volts
•
Single & Multi Outputs
•
Fully Wired Customised Racks
•
Parallel Redundant Systems
•
Euro Cassette or Wall Mount
Sp e c i f i c a t i o n
Voltage Range
•
•
•
•
See Tables of models, unit switches off at under- and overvoltage
No-Load input current
Switch-on time
Hold-up time
3% of full load current typical
100 ms typical - C300-C4700, 500 ms typical - C5600-C5800
Depends on input voltage (typ. 2 ms at 12 V DC)
Inrush current
•
Depends on impedance of supply line, see list of options for option ‘I’
High-energy pulses/surges
Spikes/bursts
•
•
•
ENV 50142 (level 3)
Acc. to IEC 1000-4-4 (level 3)
0.1%
Line regulation (± 10% )
Load regulation (10-90% )
Ripple
•
•
0.2%
≤ 1% + 30 mV p-p (0.5% typical lin. reg. aux.)
Load transient
(20-100-20% )
•
•
•
•
6% typical
Response time to ± 1%
Overload protection
Overvoltage protection
2 ms typical - C300-C4700, 10 ms typical - C5600-C5800
Current limited at 105-110% of full load (See Technical Notes s/c protection)
Standard on single output models and main output on multi output units
OVP switches off module with automatic restart
Standard on main output and all single outputs
0.02% /°C typical
Remote sensing
•
•
Temperature coefficient
Operating temperature
Storage temperature
•
•
–20 °C to +75 °C derate from +55 ºC at 2.5% /ºC (Optional -40 ºC to +75 ºC)
–40 °C to +85 °C
Relative Humidity
Efficiency at full load
Switching frequency
Isolation Voltage
EMC
•
•
•
•
•
•
•
•
•
•
5 to 95% Non Condensing
60-90% , depending on model
Approx. 33 kHz
Acc. to EN 60950 class 1
Acc. to EN 55022, level A, conducted and radiated
Approx. 100,000 hrs at 40 °C
Acc. to EN 60950 to class 1
M.T.B.F.
Construction (safety)
Creepage distance
Air distance
Acc. to VDE 0110, 4 mm
Acc. to VDE 0110, 3 mm
Connector
H 15 DIN 41612 or studs for higher current outputs C300-C4700,
studs only C5600-C5800
UK
D
Tel: +44 (0)118 984 5515
Tel: +49 (0)700 9977 1000