Bus s m a nn
Modular Fuseblocks
BH-0 Series
0-700 Volts, 100 Amps
Dim e ns iona l Da ta - All tolerances
(± 0.25) mm
(± 0.01) inches
B
71.42
54.23
2.135"
2.812"
®
B u s s
5.33 x 6.60
.21" x .26"
(Typ. 2)
53.98
2.125"
11.68 x 12.95
Ca ta log Sym bol: BH-0 Series
Ba s e : Light-weight, high temperature
thermoplastic
Mounting Studs : Plated steel
Nut: Plated steel
.46" x .51"
(Typ. 2)
Bu s s
®
A
C
Wa s he r: Spring steel
Conne c tor: Tin-plated aluminum. One
hole connector accepts #14 - 2/0 copper
wire. Two hole connector accepts #14 - 1/0
copper wire.
68.20
2.685"
Age nc y Approva l:
UL Recognized, Guide IZLT2, File E14853
up to 700 Volts
CSA Certified, Class 6225-01, File 47235
up to 700 Volts
Withs ta nd Ra ting: 200,000A RMS Sym.
or interrupting rating of fuse used, whichever
is smaller.
Te m pe ra ture Ra ting (RTI): 140°C
Ca ta log Code De s c ription:
Block Series
BH - 0 X X X S
Optional Control Wire Screw
Agency Approval
Stud Size
0 No Agency Approval
1 UL Recognition and CSA Certification
2 UL Recognition Only
1⁄Ω¢ - 20
2fiΩ¡§ - 18
3‹Ω• - 16
Wire Connector
0 No Connector
1 1 Hole for #14 - 2/0 Copper Wire
(for use with Base 0)
3 CSA Certification Only
2 2 Hole for #14 - 1/0 Copper Wire
(for use with Base 0)
NOTES: 1. Always check applicable end use standards for required spacing between blocks, fuses or other hardware.
2. For applications above 700V, consult appropriate electrical standard for proper creepage distances, clearance distances and insulator
voltage withstand ratings.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
Form No. BH-0
Page 1 of 2
12-17-98
BIF Doc #1200
SB98107