Technical data sheet
01RT-5..
Room Sensor Temperature
Passive wall mount temperature sensors
with an incorporated manual override button
and sleek design. Available with four
different outputs to be seamlessly
connected to existing third-party controllers.
Type Overview
Type
Output signal
Pt1000
01RT-5B-0
01RT-5L-0
01RT-5M-0
01RT-5Q-0
NTC10k (10k2)
NTC10k3 (Precon)
NTC20k
Technical Data
Electrical Data Electrical connection
Cable entry
Spring loaded terminal block 0.5...1.5 mm²
Wire openings at the backside (for In-wall
wiring) and top-/bottom side (for On-wall
wiring)
Functional Data
Measuring Data
Output signal passive temperature
Pt1000
NTC10k (10k2)
NTC10k3 (Precon)
NTC20k
Application
air
Measuring values
Temperature
30...120°F [0...50°C]
Measuring range temperature
Accuracy temperature passive
Measuring current
Passive Sensors depending on used type
Pt.. = ±0.5°F @ 32°F [±0.3°C @ 0°C]
NTC.. = ±0.35°F @ 77°F [±0.2°C @ 25°C]
Pt1000: <0.3 mA @ 32°F [0°C]
NTC10k2: <2 mA @ 77°F [25°C]
NTC10k3: <2.7 mA @ 77°F [25°C]
NTC20k: <0.5 mA @ 77°F [25°C]
Time Constant τ (63%) in the room
Wall Coupling Factor
Housing
typical 360 s
35 %
Materials
white, RAL 9003
www.Belimo.US
01RT-5.. • en-us • 2020-07-02 • Subject to change
1 / 3