VER : A_1
update : 94.08.25
AC-DC Switching Power Supply
ATC DN SERIES
10 Watts
KEY FEATURES
Din Rail Switching Power Supply
Universal Input Range 90-264VAC, 47-440 Hz
Regulated Output
Low Ripple and Noise
High Efficiency
CE, UL, TUV Approval
2-Years Product Warranty
ELECTRICAL SPECIFICATIONS
Model No.
( Single Output )
ATC-3.3S-DN
10W
ATC-5S-DN
10W
ATC-12S-DN
10W
ATC-15S-DN
10W
ATC-24S-DN
10.2W
Max Output Wattage (W)
Voltage
90-264 VAC or 120-370 VDC
47-440 Hz
Frequency (Hz)
Input
Current (Full load)
Inrush Current (<2ms)
Leakage Current
Voltage (V.DC.)
200 mA max. (115 VAC) / 130 mA max. (230 VAC)
10 A max. (115 VAC) /20 A max. (230 VAC)
0.75 mA max.
3.3V
5V
12V
15V
666
24V
426
Voltage Accuracy
Current (mA) max
Line Regulation (LL-HL) (typ.)
Load Regulation (5-100%) (typ.)
Minimum Load
±2%
3000
±0.3%.
±0.5%
4%
2000
833
5%
5%
3%
5%
Output
Maximum Capacitive Load
Ripple
470-23,000µF depending on model
<0.2% Vout +40mV max (Vp-p)
<0.5% Vout +50mV max (Vp-p)
Noise
Efficiency
65%
71%
73%
70%
68%
Hold-up Time
15 ms min.
100 kHz
Switching Frequency
Over Power Protection
Over Voltage Protection
Short Circuit Protection
Input-Output (V.AC)
Input-FG (V.AC)
Hiccup technique, auto-recovery
Zener diode clamp
Protection
Isolation
Hiccup mode, indefinite (automatic recovery)
3000V
1500V
Output-FG (V.AC)
Operating Temperature
Storage Temperature
Temperature Coefficient
Humidity
500V
-25°C…+70°C (with derating)
-40°C…+85°C
Environment
±0.02%/°C
95% RH
MTBF
>250,000 h @ 25°C (MIL-HDBK-217F)
Dimension (L x W x H)
Case Material
3.2 x 3.47 x 1.89 Inches ( 81.0 x 88.0 x 48.0 mm ) Tolerance ±0.5 mm
Plastic resin with Fiberglass (flammability to UL 94V-2)
Physical
Weight
180 g
Cooling Method
Free air convection
UL/cUL, CE, TUV
EN 55022 class B
EN 50082-1
Safety
EMC
Agency Approvals
EMI (Conducted & Radiated Emission)
EMS (Noise Immunity)
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.archcorp.com.tw
TEL: +886-2-26989508 FAX: +886-2-26981319
-1-