GAMEWELL-FCI 装置
页数 文件大小 规格书
4页 278K
描述
Wheelock AS Series Audible Strobe Devices & AH Series Audible Devices

ASWP-2475W-FR 数据手册

 浏览型号ASWP-2475W-FR的Datasheet PDF文件第2页浏览型号ASWP-2475W-FR的Datasheet PDF文件第3页浏览型号ASWP-2475W-FR的Datasheet PDF文件第4页 
Features  
Wheelock AS Series Audible Strobe  
• ADA/NFPA/UFC/ANSI Compliant  
AS Series Audible Strobe  
Devices are available in wall  
and ceiling-mount models:  
Wall mount models offered  
are available with Field  
Devices & AH Series Audible Devices  
Selectrable Candela Settings of  
15/30/75/110cd or 15/75cd  
(single candela model)  
Description  
Ceiling mount models  
offered are available with field  
selectrable candela settings of  
15/30/75/95cd  
Wheelock’s patented 2-wire AS Series Audible  
Strobe Applicances and AH Series Audible Devices  
offer more features with low current draw.  
Strobe options for wall mount models include 15/  
75cd or Wheelock’s patented MCW multi-candela  
wall strobes with field selectrable candela settings  
of 15/30/75/110cd.  
• Selectable Continous Horn or  
Temporal (Code 3)  
• 3 Selectable dBA settings (99,  
95 and 90 dBA) in both tones  
Patented 2-Wire Audible  
Strobe Appliance  
Ceiling mount models incorporate Wheelock’s pat-  
ented MCC multi-candela ceiling strobe with field  
selectrable intensities of 15/30/75/95cd.  
AS Audible  
Strobe  
• Patented Universal Mounting  
Plate  
The audible provides a selectable choice of either  
a continous horn or temporal pattern (Code 3) when  
constant voltage from a Fire Alarm Panel (FACP) is  
applied. Each tone has 3 dBA settings to choose  
from.  
• Weatherproof models are  
available for outdoor use  
• Strobes produce 1 flash per  
second over the regulated voltage  
range  
When used with the Wheelock Series SM or DSM  
Sync Module or with a power supply with the  
Wheelock sync protocol, synchronization of the  
continous horn tone provides the temporal (code 3)  
tone (mandated by NFPA 72) simultaneously for all  
audible appliances. This ensurses a distinct tem-  
poral (code 3) pattern when 2 or more audibles are  
within hearing distance. If not synchronized the tem-  
poral sound could overlap and not be distinctive. At  
the same time the strobes will be synchronized.  
This provides the ability to comply with ADA guide-  
• 12 and 24 VDC models with wide  
UL “Regulated Voltage Range”  
using filtered DC or unfiltered  
FWR input voltage  
• Synchronize with Wheelock SM,  
DSM or power supply with built-  
in Wheelock sync protocol  
• Fast installation with IN/OUT  
screw terminals using #12 and  
#18 AWG wires  
AH Audible  
lines concerning photosensitive epilepsy and the NFPA standards when install-  
ing 2 or more visual appliances within the field of view all of this plus the ability to  
silence the audible is achieved using only 2 wire.  
Listings  
Listings and approvals below  
apply to the basic Wheelock AS  
SeriesAudible Strobe Devices  
andAH SeriesAudible Devices.  
In some cases, certain modules  
may not be listed by certain  
approval agencies, or listing may  
be in process. Consult factory for  
latest listing status.  
General Notes  
• Strobes are designed to flash once per second minimum over the Regulated  
Voltage Range. Note that NFPA-72 (1999) specifies a flash rate of 1 to 2  
flashes per second and ADA Guildelines specify a flash rate of 1 to 3 flashes  
per second.  
• All candela ratings represent minimum effective Strobe intensity based on UL  
Standard 1971.  
• AS Series Strobe products are listed under UL Standard 1971 for indoor use  
with a temperature range of 32° F to 120° F (O° C to 49° C) and maximum  
humidity of 93% (+ 2%)  
• UL Listed: file E5946.  
• ULC Listed: file CS356.  
• MEA approved: file 152-92-E.  
• AH-24 Series horns are listed under UL Standard 464 for audible signal  
appliances (indoor use only).  
• CSFM approved: file 7125-  
• AH-24WP Series audible appliances are listed under UL Standard 464 for  
indoor/outdoor use with a temperature range of -31° F to 150° F (-35° C to 66°  
C) and maximum humidity of 95%.  
0785:131  
“Regulated Voltage Range” is the newest terminology used by UL to  
identify the voltage range. Prior this change, UL used the terminology  
“Listed Voltage Range”.  
AS Series & AH Series CS-2231 06/01/04  
Page 1 of 4  

与ASWP-2475W-FR相关器件

型号 品牌 获取价格 描述 数据表
ASWR02HB1 TOKO

获取价格

RF/Microwave Antenna, 2400MHz Min, 2500MHz Max
ASWR02HB2 TOKO

获取价格

RF/Microwave Antenna, 2400MHz Min, 2500MHz Max
ASWR02HP1 TOKO

获取价格

RF/Microwave Antenna, 2400MHz Min, 2500MHz Max
ASWR02HP2 TOKO

获取价格

RF/Microwave Antenna, 2400MHz Min, 2500MHz Max
ASWR03 TOKO

获取价格

2.45 GHZ DIELECTRIC ANTENNA
ASX20003 NAIS

获取价格

HIGH SENSITIVITY RELAY WITH GUARANTEED LOW LEVEL SWITCHING CAPACITY
ASX20003 PANASONIC

获取价格

Power/Signal Relay, DPDT, Momentary, 0.017A (Coil), 3VDC (Coil), 50mW (Coil), 0.01A (Conta
ASX20006 PANASONIC

获取价格

Power/Signal Relay, DPDT, Momentary, 0.008A (Coil), 6VDC (Coil), 50mW (Coil), 0.01A (Conta
ASX20006 NAIS

获取价格

HIGH SENSITIVITY RELAY WITH GUARANTEED LOW LEVEL SWITCHING CAPACITY
ASX20009 NAIS

获取价格

HIGH SENSITIVITY RELAY WITH GUARANTEED LOW LEVEL SWITCHING CAPACITY