ASIA
EUROPE
Units 2111-2116, Level 21
Tower1, Metroplaza
223, Hing Fong Road
Fwai Fong, New Territories
Hong Kong
AMERICAS
Astec House, Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX, UK
Telephone: 44 (1384) 842-211
Facsimile: 44 (1384) 843-355
5810 Van Allen Way
Carlsbad, CA 92008
Telephone: 760-930-4600
Facsimile: 760-930-0698
48V 400-600 Amp
Telephone: 852-2437-9662
Facsimile: 852-2402-4426
Breaker Panel (BIP)
AP6C64AA
A breaker interface panel, also knows as a power distribution unit
(PDU), or frame supervisory panel (FSP), improves system power
stability and provides a convenient centralized location for all
customer load circuit breakers, alarms, and filtering.
Electrical Specs
INPUT
DC input
Transients
Input feeds
-40 VDC to –75 VDC
ANSI T1.315-1994, FTZ19, BTR2511
4 x 100A each
4 x 150A each (available in the future)
OUTPUT
DC output
20 x 25A breakers total
Four breaker modules,
each with 5 x 25A breakers
Alarm signals
Critical, major, minor alarms
Special Features
• Low profile:
•
•
Fits in 2U height,
3.47", 88.1 mm
Environmental
• 23" width
• 4 x 100 A input feeds, upgradeable to 4 x 150A
input feeds
EMC/EMI:
ESD:
No switching components, inherently
EMI/EMC benign
• supports A & B redundant input feeds
•
4 hot swappable Breaker Modules + one Alarm
Module
Bellcore GR-1089-CORE, ETSI 300 386-1,
(15kV)
• Breaker Modules available in various configurations,
all come equipped with:
Operating Temperature and Humidity
-5°C to +55°C normal, 5% to 85% RH, non-condensing
-8°C to +65°C short term
•
•
•
28,200 µF capacitor bank
automatic inrush current limiting
hot swappable, field replaceable without
service interruption
Shock and
Vibration:
Bellcore GR-063-CORE and ETSI 300 019
Zone 4 earthquake
• Breaker Module configurations:
•
•
•
•
•
•
•
5A 5A 5A 5A 5A
20A 20A 20A 20A 20A
25A 25A 5A 25A 25A
10A 5A 30A 5A 10A
25A 25A 25A 25A 25A
30A 30A 5A 30A 30A
other configurations available on request,
please consult your Astec representative
Fire Resistance: UL94V-0
Safety
UL
CSA
EN
1950
C22.2 950
60850, 41003
GR-063-CORE
• Standard Alarm module comes equipped with:
•
•
•
•
•
•
•
•
isolated alarm contacts
input feed fail alarm
output breaker trip alarm
critical, major, minor alarms
end aisle lamp drive
fully programmable, 6 bit, shelf ID
LED test switch
connections for voice and data jacks
Bellcore
• Enhanced, customized alarm modules available by
special order
182
America’s (USA): 1-888-41-ASTEC
Europe (UK): 44 (1384) 842-211
Asia (HK): 852-2437-9662
rev 12.01.01