5秒后页面跳转
ANR-112-C PDF预览

ANR-112-C

更新时间: 2022-05-14 21:55:01
品牌 Logo 应用领域
爱模 - MSYSTEM /
页数 文件大小 规格书
4页 124K
描述
Limit Alarms (potentiometer adj.) A-UNIT

ANR-112-C 数据手册

 浏览型号ANR-112-C的Datasheet PDF文件第2页浏览型号ANR-112-C的Datasheet PDF文件第3页浏览型号ANR-112-C的Datasheet PDF文件第4页 
MODEL: ANR  
3: Lo (coil energized at alarm)  
Limit Alarms (potentiometer adj.) A-UNIT  
4: Lo (coil de-energized at alarm)  
ANGLE SENSOR ALARM  
Functions & Features  
[4] POWER INPUT  
AC Power  
• Providing SPDT relay outputs at preset voltage level  
provided from Angle Sensor (model: NRA)  
• Dual (Hi/Lo) trip  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
• Energized or de-energized coil at a tripped condition  
selectable  
• 50 % zero/span adjustments  
• Hysteresis (deadband) adjustable  
• Enclosed relays  
DC Power  
• Relays can be powered 110 V DC  
• High-density mounting  
S: 12 V DC  
R: 24 V DC  
V: 48 V DC  
Typical Applications  
• Annunciator  
P: 110 V DC  
• Various alarm applications  
RELATED PRODUCTS  
• Brushless angle sensor (model: NRA)  
50  
(1.97)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
80  
(3.15)  
Connection: M3.5 screw terminals  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output 1 to output 2 to power  
Zero adjustment: 0 – 50 % of linearity-assured range of the  
angle sensor (front)  
136  
(5.35)  
mm (inch)  
Span adjustment: 50 – 100 % of linearity-assured range of  
the angle sensor (front)  
MODEL: ANR-[1]1[2][3]-[4]  
Setpoint adjustments: 270°-turn screwdriver adjustments  
(front); 0 – 100 % independently  
ORDERING INFORMATION  
• Code number: ANR-[1]1[2][3]-[4]  
Specify a code from below for each of [1] through [4].  
(e.g. ANR-1111-B)  
Hysteresis (deadband) adjustments: 1 – 100 % (front)  
LEDs: LED turns on at a tripped condition; red for output 1,  
green for output 2 (located behind the front cover)  
Power ON timer: Relays de-energized for approx. 2 seconds  
after power is turned on.  
[1] ACTION  
1: Direct (output increases with input increase)  
INPUT SPECIFICATIONS  
Input: 2 – 3 V DC (output from Angle Sensor)  
Excitation: 5 V DC ±2 %  
2: Reverse (output increases with input decrease)  
[2] SETPOINT 1 OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
3: Lo (coil energized at alarm)  
4: Lo (coil de-energized at alarm)  
[3] SETPOINT 2 OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
ANR SPECIFICATIONS  
ES-2116 Rev.2 Page 1/4  
http://www.m-system.co.jp/  

与ANR-112-C相关器件

型号 品牌 描述 获取价格 数据表
ANR-112-D MSYSTEM Limit Alarms (potentiometer adj.) A-UNIT

获取价格

ANR-112-F MSYSTEM Limit Alarms (potentiometer adj.) A-UNIT