5秒后页面跳转
ACM-8RF PDF预览

ACM-8RF

更新时间: 2022-12-17 00:52:57
品牌 Logo 应用领域
其他 - ETC 继电器
页数 文件大小 规格书
2页 447K
描述
RELAY MODULE FOR USE WITH MS-9200 MS-9200UD MS-9600 AND MS-5210UD

ACM-8RF 数据手册

 浏览型号ACM-8RF的Datasheet PDF文件第2页 
July 13, 2004  
DF-51555 • B-500  
ACM-8RF  
Relay Module for use with MS-9200,  
MS-9200UD, MS-9600 and MS-5210UD  
www.firelite.com  
Section: Annunciators  
GENERAL  
The ACM-8RF is a relay module in the Fire•Lite AFM Se-  
ries of annunciators. It provides the MS-9200, MS-9200UD  
and MS-9600 Fire Alarm Control Panels and MS-5210UD  
10-zone Fire Alarm Control/Communicator with relay-by-  
zone capability for elevator recall, HVAC control, etc. The  
ACM-8RF provides eight (8) Form-C mappable relays with  
contacts rated at 5 amps. The ACM-8RF mounts remote  
from the MS-9200, MS-9200UD, MS-9600 and MS-5210UD  
in an ABS-8RF enclosure.  
MEA  
122-96-E, Vol. II  
CS68/CS702  
S624  
California  
State Fire  
Marshal  
7120-0075:178  
Up to 32 ACM-8RF relay modules may be installed on the  
panel’s EIA-485 circuit.  
FEATURES  
• Provides eight Form-C relays with 5-amp contacts.  
• Up to 32 ACM-8RFs may be installed on the MS-9200,  
MS-9200UD, MS-9600 and MS-5210UD’s EIA-485 se-  
rial output.  
• Mounts remotely in ABS-8RF enclosure.  
• Requires only two wires for communication and two for  
power.  
• Removable terminal blocks for ease of installation and ser-  
vice.  
• DIP switch selectable memory mapping of relays.  
MOUNTING  
The ACM-8RF will only mount to an ABS-8RF annunciator  
surface-mount backbox with blank faceplate.  
OPERATION  
Communication between the Control Panel and the ACM-  
8RF is accomplished over a two-wire EIA-485 serial inter-  
face. This communication, to include the wiring, is super-  
vised by the fire alarm control panel. Power for the relay  
module is provided via a separate power loop from the con-  
trol panel which is inherently supervised (loss of power also  
results in a communication failure at the control panel).  
RELAY MAPPING  
The ACM-8RF’s relays follow the status of the 56 software  
zones of the MS-9200, the 99 software zones of the MS-  
9200UD and MS-9600 or the 10 Initiating Device Circuits  
(IDCs) of the MS-5210UD. For full relay-by-zone capability  
with the MS-9200 (i.e., 56 software zones), a minimum of  
seven ACM-8RFs are required (alarm only). For full Relay-  
By-Zone capability with MS-9200UD and MS-9600, a mini-  
mum of 13 ACM-8RF’s are required(alarm only). For full  
MS-5210UD relay-by-zone capability (i.e., all 10 zones), a  
minimum of two ACM-8RFs are required (alarm only).  
Consult the ACM-8RF installation manual for application-  
specific details.  
ACM-8RF  
Fire•Lite® Alarms is a Honeywell company.  
This document is not intended to be used for installation purposes. We try to keep  
our product information up-to-date and accurate. We cannot cover all specific  
applications or anticipate all requirements. All specifications are subject to  
change without notice.  
For more information, contact Fire•Lite Alarms, One Fire-Lite Place, Northford,  
Connecticut 06472. Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105.  
Made in the U.S.A.  
DF-51555 • 07/13/04 — Page 1 of 2  

与ACM-8RF相关器件

型号 品牌 描述 获取价格 数据表
ACM9070 TDK Common Mode Filters For power line ACM series

获取价格

ACM9070-142-2P-T TDK Common Mode Filters

获取价格

ACM9070-142-2P-TL TDK Common Mode Filters

获取价格

ACM9070-701-2PL TDK Common Mode Filters(SMD)

获取价格

ACM9070-701-2PL-TL01 TDK Common Mode Filters For power line ACM series

获取价格

ACM9070-701-2PL-TL01_16 TDK Common Mode Filters For power line

获取价格