描述
Intelligent Low-Flow Photoelectric Duct Smoke Detectors

M02-04-00 数据手册

 浏览型号M02-04-00的Datasheet PDF文件第2页浏览型号M02-04-00的Datasheet PDF文件第3页浏览型号M02-04-00的Datasheet PDF文件第4页 
SS-PD and SS-PDR  
Intelligent Low-Flow Photoelectric  
Duct Smoke Detectors  
Features  
• Air velocity rating from 100 to  
4,000 feet per minute (0.5 to  
20.32 m/sec.).  
• Patented telescopic sampling  
tube.  
SS-PD  
• Easily accessible code wheels  
for addressing detector.  
Description  
The Gamewell SS-PD and SS-PDR  
• Outside mounting tabs.  
Intelligent Low-Flow Photoelectric  
Smoke Duct Detectors provide low-  
flow technology that enables duct  
smoke detection throughout a broad  
range of airflow environments in HVAC  
applications. The low-flow technology  
can detect smoke at air speed veloci-  
ties of 100 feet per minute (0.5 m/sec.)  
or greater, while continuing the same  
reliable performance to 4,000 feet per  
minute (20.32 m/sec.). The intelligent  
low-flow duct detectors sample air cur-  
rents passing through a duct and gives  
dependable performance for shutdown  
• Mounts to round or rectangular  
ducts from 1’ to 12’ (0.3 to 3.7  
meters) wide.  
• Transparent cover for conve-  
nient visual inspection.  
SS-PDR  
Listings  
Listings and approvals below  
apply to the SS-PD and SS-  
PDR Intelligent Low-Flow  
Photoelectric Duct Smoke  
Detectors. In some cases,  
certain modules may not be  
listed by certain approval  
agencies, or listing may be in  
process. Consult factory for  
of fans, blowers, and air conditioning systems, preventing the spread of toxic smoke  
an fire gases through the protected area.  
The SS-PD and SS-PDR provide a remote alarm output for use with auxiliary  
devices such as the RA400 remote LED annunciator, as well as remote test capa-  
bility with the RTS451 or RTS451KEY Remote Test Stations.  
The SS-PD is a photoelectric duct detector with SmartScanTM protocol. The SS-  
latest listing status.  
PDR additionally incorporates a relay.  
• UL Listed: file S1115.  
Applications  
• CSFM approved:  
file 3240-1288:167.  
Duct smoke detectors have specific limitations, they are:  
NOT a substitute for open area smoke detectors.  
NOT a substitute for early warning detection.  
• MEA approved: file 384-02-E  
Vol. III.  
NOT a replacement for a building’s regular fire detection system.  
Please call Gamewell for a copy of System Sensor’s application guide, Proper Use  
of Smoke Detectors in Duct Applications, (A05-1004-00).  
Installation  
Wiring: For signal wiring (the wiring between detectors or from detectors to auxil-  
iary devices), it is recommended that single conductor wire be no smaller than 18  
AWG (0.75 mm²). The duct smoke detector terminals accommodate wire sizes up  
to 12 AWG (3.25 mm²). Flexible conduit is recommended for the last foot (30.48  
cm) of conduit; solid conduit connections may be used if desired.  
Smoke detectors and alarm system control panels have specifications for Signal-  
ing Line Circuit (SLC) wiring. Consult the control panel specifications for wiring  
requirements before wiring the detector loop. The SS-PD and SS-PDR detectors  
are designed for ease of wiring; their housing provides a terminal strip with clamp-  
ing plates.  
LED Features: If programmed with the system control panel, two LEDs on each  
duct smoke detector light to provide local visible indication.  
Page 1 of 4  
SS-PD and SS-PDR CS-2463 10/21/04  

与M02-04-00相关器件

型号 品牌 描述 获取价格 数据表
M02-04-01 GAMEWELL-FCI Filtrex Hostile Area Smoke Head Analog Addressable Detector with SmartScan

获取价格

M02-04-01 SYSTEMSENSOR Intelligent Photoelectric Smoke Detector

获取价格

M02040-15 TE 3.3 5V Limiting Amplifier for Applications to 2.125 Gbps

获取价格

M02040-15EVM TE 3.3 5V Limiting Amplifier for Applications to 2.125 Gbps

获取价格

M02044CG-31 TE 3.3/5V Limiting Amplifier for Applications from 100 Mbps to 622 Mbps

获取价格

M02044CG-31EVM TE 3.3/5V Limiting Amplifier for Applications from 100 Mbps to 622 Mbps

获取价格