描述
MOTOR REPLACEMENT

40002737-001 数据手册

 浏览型号40002737-001的Datasheet PDF文件第2页 
INSTALLATION  
INSTRUCTIONS  
V4073A Motorised Mid-Position Valve  
Application  
The V4073A valve has been designed to control the flow of  
water in a small bore domestic central heating system where  
both radiator and hot water cylinder circulation are pumped.  
It is typically suited for systems up to 90,000 Btu/h (26 KW).  
Specifications  
Voltage: 230-240V ~ 50Hz  
Power consumption: 6W  
Lead supplied: 1 metre, 5 core  
Operating temperature range: +5 to +88°C  
(Special models available for chilled water applications)  
Maximum ambient temperature: +52°C  
Pipe fitting sizes:  
22mm & 28mm compression fitting, / " & 1" BSP  
3
4
Dimensions and KV values: See diagrams  
Spares available  
Powerhead  
Part No. 40003916-003  
Part No. 40002737-003  
Part No. 272742A CARD  
Motor  
Ball & ‘O’ Ring Kit  
Installation  
V4073A incorporates a manual  
lever, the lever should normally  
be in ‘AUTO’ position, but can  
be moved to ‘MAN OPEN’  
position for system draindown  
and filling purposes only.  
AUTO  
MAN  
OPEN  
Before fitting the valve, read  
through the plumbing and  
wiring instructions.  
This product MUST be  
installed by a competent  
person. The installation MUST conform to I.E.E.  
Regulations and with The Electricity at Work Regulations.  
A Class ‘A’ switch (having contact separation of at least  
3mm in all poles) must be incorporated in the fixed wiring  
as a means of disconnecting the supply. The system must  
be appropriately fused.  
Flow  
Characteristics  
Plumbing  
The valve MUST NOT be fitted on the return pipework  
under any circumstances. Flow from the boiler must be  
connected to port AB, the radiator circuit to port A and the  
hot water cylinder circuit to port B.  
The valve may be plumbed in at any angle but must not be  
mounted so that the valve head is below the horizontal  
level of the pipework. In the unlikely event of a leak a  
safety hazard could result.  
Do not grip the valve head while making and tightening up  
1
4
plumbing connections. Attach a spanner (32mm or 1 / " AF)  
onto the valve body at each port, whilst tightening up the nuts.  
Tighten compression nuts enough to make a watertight seal.  
TAKE CARE NOT TO OVERTIGHTEN.  

与40002737-001相关器件

型号 品牌 描述 获取价格 数据表
40002A01 ICSI FEMTOCLOCKS? CRYSTAL-TO LVCMOS/LVTTL FREQUENCY SYNTHESIZER

获取价格

40004000/10MM ETC NYLON66 ERTALON L 1M D 10MM Inhalt pro Packung: 5 Stk.

获取价格

40004000/15MM ETC NYLON66 ERTALON L 1M D 15MM Inhalt pro Packung: 3 Stk.

获取价格

40004000/20MM ETC NYLON66 ERTALON L 1M D 20MM Inhalt pro Packung: 2 Stk.

获取价格

40004000/25MM ETC NYLON66 ERTALON L 1M D 25MM Inhalt pro Packung: 2 Stk.

获取价格

40004000/30MM ETC NYLON66 ERTALON L 1M D 30MM Inhalt pro Packung: 2 Stk.

获取价格