描述
Four-Zone Fire Alarm Control Panel

4XTMF 技术参数

是否无铅: 不含铅是否Rohs认证: 符合
生命周期:Active包装说明:ROHS COMPLIANT
Reach Compliance Code:unknownECCN代码:EAR99
HTS代码:8536.69.40.40风险等级:2.29
其他特性:LOW PROFILE连接器类型:BOARD CONNECTOR
联系完成配合:NOT SPECIFIED触点性别:MALE
触点材料:NOT SPECIFIEDDIN 符合性:NO
滤波功能:NOIEC 符合性:NO
MIL 符合性:NO混合触点:NO
安装方式:STRAIGHT安装类型:CABLE
装载的行数:1选件:GENERAL PURPOSE
端子节距:1.5 mm端接类型:CRIMP
触点总数:4UL 易燃性代码:94V-0
Base Number Matches:1

4XTMF 数据手册

 浏览型号4XTMF的Datasheet PDF文件第2页 
Features  
Four Style B (Class B) Initiating Device Circuits  
(IDCs); two Style Y (Class B) Notification  
Appliance Circuits (NACs); optional module (P/  
N CAC-4) converts 4 IDCs and two NACs to  
Class A. 24 VDC.  
Flex 404  
Four-Zone Fire Alarm Control Panel  
NAC synchronization features:  
– Provides synchronization of standardANSI  
audible signals as required by NFPA 72  
(3-8.4.1.2.3).  
– Provides synchronization of ADAcompliant  
strobes per NFPA72 (4-4.4.1).  
Description  
The Gamewell Flex 404 Fire Alarm  
– Selectable for System Sensor, Cooper-  
Wheelock,& Gentex protocols.  
– Selective Silence feature allows manual  
silencing of horns while strobes continue to  
flash on the same NAC.  
Control Panel brings the latest in mi-  
croprocessor technology to conven-  
tional fire controls. The Flex 404 is  
compatible with the new i³  
smoke  
detectors from System Sensor, and  
provides advanced features including  
drift compensation, maintenance alert,  
and freeze warning. Automatic syn-  
chronization of audio/visual devices is  
provided, selectable for three manufac-  
turers’ protocols. The NAC protocol in-  
cludes the ability, using a single pair  
of wires, to silence audible devices  
Silent orAudible WalkTest operation mode  
commanded from the front keypad, with  
automatic return to normal after one hour of  
inactivity.  
Alarm verification selectable per zone.  
Each zone may be programmed for supervisory  
or fire; each zone has separate red and yellow  
LEDs.  
Disable switches provided for each zone.  
NACs programmable for: Silence Inhibit,Auto  
Silence, Strobe Synchronization, Selective  
Silence (horn/strobe mute), Temporal or  
Steady signal, Silenceable or Nonsilenceable.  
Form-CAlarm, Trouble, and Supervisory  
relays.  
3.0A(6.0Awith optional second transformer)  
total usable current.  
Piezo sounder for alarm, trouble, supervisory,  
and maintenance.  
Control buttons:ACK (Acknowledge),Alarm  
Silence, Reset, Walktest, Zone Enable/Disable  
(one per zone).  
LED indicators: FireAlarm (one per zone),  
Supervisory (one per zone), Trouble (one per  
zone), Maintenance (one per zone),AC  
Power, NAC Disable, Zone Disable, NAC  
Fault, System Trouble, Power Trouble,  
Walktest,Alarm Silence, Earth Fault (on circuit  
board), Battery Fault (on circuit board),  
Charger Fault (on circuit board).  
while strobes continue to flash.  
The Flex 404 is also compatible with conventional input devices such as two-  
and four-wire smoke detectors, pull stations, waterflow devices, tamper switches  
and other normally-open contact devices.  
Operation  
The activation of a compatible smoke detector or any normally-open fire alarm  
initiating device will: activate audible and visual signaling devices, illuminate an  
indicating LED, sound the piezo sounder at the FACP, activate the FACP alarm  
relay, and operate an optional module which notifies a remote station or initiates  
an auxiliary control function.  
Technology Features  
• Drift compensation automatically adjusts detector sensitivity and increases  
resistance to false alarms caused by dust accumulation.  
• The maintenance alert LEDs (per zone) warn of excessive dirt accumulation,  
preventing false alarms.  
Optional dress panel (P/N DP-FLEX).  
Optional modules: plug-in transmitter module  
(P/N 4XTMF); plug-in zone relay module  
(P/N 4XZMF); transmitter module (P/N  
4XLMF) for SAN-404 remote LED annuncia-  
tor.  
• Detector sensitivity is automatically measured. The twice-yearly test require-  
ments of NFPA72 (7-3.2.1) are met without using a ladder or test meter.  
• The wireless handheld sensitivity meter eliminates the need for voltmeters,  
magnets, or a physical connection to the detector. The reader displays sensi-  
tivity in terms of percent-per-foot obscuration and provides text status indica-  
tion.  
Listings  
Listings and approvals below apply to the  
basic Flex 404 panel. In some cases, certain  
modules may not be listed by certain approval  
agencies, or listing may be in process.  
Consult factory for latest listing status.  
• The supervisory LED (per zone) provides a warning if a detector senses tem-  
peratures approaching freezing.  
UL Listed: file S521.  
CSFM approved: file 7165-1288:180.  
MEA approved: file 366-04-E.  
• Special test protocol and LED indication allow a quick test of all detectors —  
without a ladder.  
• Electronic heat-sensing element provides thermal detection in addition to pho-  
toelectronic smoke detection.  
Flex 404 Four-Zone FACP CS-2404 09/01/06  
Page 1 of 2  

与4XTMF相关器件

型号 品牌 描述 获取价格 数据表
4XZMF HONEYWELL 2 and 4 Zone Conventional Fire Alarm Control Panels

获取价格

4XZMF GAMEWELL-FCI Four-Zone Fire Alarm Control Panel

获取价格

5,08R29 LUMBERG Board Connector, 29 Contact(s), 1 Row(s), Female, Straight, Solder Terminal, Socket

获取价格

5,08RF LUMBERG Board Connector, 31 Contact(s), 1 Row(s), Female, Straight, Solder Terminal, Socket

获取价格

5,08RF14 LUMBERG Board Connector, 14 Contact(s), 1 Row(s), Female, Straight, Solder Terminal, Socket

获取价格

5,08RF18 LUMBERG Board Connector, 18 Contact(s), 1 Row(s), Female, Straight, Solder Terminal, Socket

获取价格