V-EA-Series - UL508 Manual Motor Controller - 3 pole B-Trip
V-EA-B Trip
1.0A Through 10A Rated Current
Rated
Current
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
Type/
1.13-1.45xIN
Cat. No.
3B1UM
3B1.6UM
3B2UM
3B2.5UM
3B3UM
3B3.5UM
3B4UM
3B5UM
3B6UM
NA
Approvals
UL508 Listed
60
40
E137938
10
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
4
1
Standard Pack: 6
Weight:
10
4
0.3A - 32A
1.8kg (3.97 lb.)
40A - 63A
1
0.4
1.98kg (4.37 lb.)
3B10UM
NA
10-1
12A
13A
4x10-2
Three Pole
3B13UM
3B15UM
3B16UM
3B20UM
3B25UM
3B30UM
3B32UM
3B40UM
3B50UM
3B60UM
3B63UM
10-2
15A
16A
4x10-3
20A
25A
10-3
1
2
3
4
5 6 8 10
20
40
100
Multiple of Rated Current
30A
32A
35 mm
V-EA-B Trip
13A Through 63A Rated Current
40A
50A
(1.38 in.)
93.3 mm
(3.67 in.)
1.13-1.45xIN
60A
63A
60
40
10
74.7 mm
(2.94 in.)
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
1
52.5 mm
4
(2.07 in.)
10
4
Voltage Rating
480Y/277VAC
0.3-25A: 1 pole - 42VDC; 2 Pole - 80VDC
30-60A: 1 pole - 24VDC; 2 Pole - 60VDC
1
0.4
10-1
Short Circuit Withstand Rating
(UL/CSA - Ratings)
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
4x10-2
10-2
Group Short Circuit Withstand Rating
(UL/CSA - Ratings)
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
4x10-3
Interrupting Capacity (VDE - Ratings)
Calibration Temperature
Operating Temperature
Storage Temperature
0.3-63A (RC): 10kA
10-3
1
2
3
4
5 6 8 10
20
40
100
40°C (104°F)
Multiple of Rated Current
-25°C to 55°C (-13°F to 131°F)
-40°C to 70°C (-40°F to 158°F)
Terminal Size Acceptability
Terminal Torque
Top: 18-3 AWG; Bottom: 18-2 AWG (Line/Load reversible)
20 lb.in.
IP20
Standard Dual
Connection Terminal
All parts are ring tongue compatible.
Terminal Protection Degree
short circuit Withstand ratings for v-ea manual motor controller
Backup
Protection
UL-Listed
RK5-Fuse
up to 10kA
UL-Listed
MCCB
up to 10kA
No BCP
Required
up to:
Trip
Curve
Ring
tongue
Amp Range
0.3 - 10A
all
all
all
all
4xRC*
min 15A, max 70A
4xRC*
min 15A, max 70A
10kA
5kA
5kA
5kA
Box
clamp
12 - 30/32A
40 - 50A
4xRC*
max 125A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 200A
60 / 63A
4xRC*
max 250A
4xRC*
max 250A
*up to nearest rated current