UR Series
UL1077 Recognized
Supplementary Protector
• DIN Rail Mounted
• 17.5mm width per pole
• Thermal Magnetic
• Current Limiting
• 0.5-60A / 480Y/277V AC,
50/60Hz
• 10kA Short Circuit
Withstand Capacity
• Applications (on the load side
of Branch Circuit Protection)
include: Sensitive Electronics,
Power Supplies, Appliance
circuits, etc.
PENDING
E137915
UR - Series
Voltage Rating
0.5-60A / 480Y/277V AC
0.5 - 10A (RC): 10 kA with no back-up fuse
8 - 63A (RC): 10 kA with UL-listed Class J back-up fuse;
5 kA with no back-up fuse
Short Circuit Withstand Rating
30ºC (86ºF)
Calibration Temperature
Ambient Temperature
Storage Temperature
Terminal Torque (min/max)
Electrical Life
-25ºC to +55ºC (-13ºF to 131ºF )
-40ºC to +70ºC (-40ºF to 158ºF )
2 Nm (17.7 lb.in.) / 2.5Nm (22.2 lb.in)
6000 switching cycles ON/ OFF
10000 switching cycles ON/ OFF
Mechanical Life
> 15g according to DIN EN 60069-2-59 during a load with 1.05 x I
Vibration Resistance
Resistance to mechanical shocks
N
25g @ 11ms
Short Circuit Withstand Ratings for R-Series Supplementary Protector
Backup Protection
Trip
Amp
UL-Listed
Class J Fuse
up to 10kA
No Backup Fuse
Curve
Range
Required
up to:
All
0.5 - 10A
12 - 60A
70A
10kA
All
4xRC*
5kA
*up to nearest rated current
For the latest on Altech Circuit Breakers specifications please visit www.altechcorp.com/breaker.
36
9