1φ 3φ 1000A AC Power Clamp Meter
Measures Current, Insulation Resistance, Temperature (Type K) and Power
Including True Power, Apparent Power, and Reactive Power
380976-K Features:
• Large dual LCD display (9999 count)
• Measures 1ϕ/3ϕ True Power (kW), Apparent Power (kVA),
and Reactive Power (kVAR), plus Horsepower (HP),
Power Factor, and Phase Angle with Lead/Lag indicator
• AC+DC μA current with 10nA resolution for flame rod tests
• Max/Min recording with elapsed time indication
• Auto Detect AC/DC Voltage measurements
with simultaneous frequency display
• Capacitance to 7000μF with 0.001μF resolution
• High Resistance tests to 100MΩ
• Type K, °C/°F switchable, temperature to 1000ºF
• Diode and Continuity tests
• Auto power off with disable feature
• 1.6" (40mm) clamp jaw opening
• Test Lead Kit includes: two CAT IV-600V 72” (1.8m) lead
extensions with right angle and straight end shrouded banana
plugs; two modular test probe handles with stainless steel
tips; two plunger activated retractable jaw clips; two extra
large alligator clips
• Complete with test lead kit, general purpose Type K
thermocouple probe, carrying case, and 9V battery
Applications:
• AC Power evaluation
• Motor/Generator installation and repair
• HVAC flame rod tests
• Capture max/min temperature or current values
• Category III rating for industrial measurements
Function
True Power (W):
Max Range / Resolution
600kW / 10W
Basic Accuracy
±±5
Apparent Power(kVA):
Reactive Power (kVAR)
Horsepower (HP)
Phase Angle (f):
AC Current: (Trms):
uA Current (AC+DC) (Trms):
AC/DC Voltage: (Trms):
Resistance (Ω):
600kVA / 100VA
600kVAR/10VAR
800HP/0.01HP
-60 to +60° / 0.1°
1000A / 10mA
1000μA / 10nA
±ꢀ5
±±5
±±5
±6°
±ꢀ5
±15
±15
±15
600V / 0.1mV
1000kΩ / 0.1Ω
Resistance (MΩ):
Capacitance:
Frequency:
100MΩ / 1kΩ
7000μF / 1nF
±±5
±1.±5
±0.±5
±15
40Hz to 1kHz / 0.1Hz
-±8 to 1000°F / 0.1°F
-±0 to 900°C / 0.1°C
9 x 3 x 1.6" (ꢀꢀ8 x 76 x 39mm)
16.4oz (46±g)
Temperature (Type K):
True Power and Phase Indication for enchanced
versatility and performance.
±15
Dimensions:
Weight:
Ordering Information:
380976-K..............3-Phase True RMS Power Clamp Meter Kit
380976-K-NIST ....380976-K w/ Calibration Traceable to NIST Standards
480172..................AC Line Splitter
Specifications subject to change without notice.
Copyright © 2008-2011 Extech Instruments Corporation. All rights reserved including the right of reproduction in whole or in part in any form.
07/ꢀ0/11 - R1
www.extech.com