Thermal-Magnetic Circuit Breaker 3500
Description
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
snap action mechanism and two button operation (M-type TM CBE
to EN 60934). Featuring a flange for panel mounting and optional
auxiliary contacts. Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Control systems, instrumentation, medical equipment, machine tools,
robotics, communications systems.
1
Ordering information
3500
Type No.
3500 standard version
Terminal design
Technical data
P10 blade terminals 6.3-0.8 (QC .250), tinned
Auxiliary contacts (optional)
For further details please see chapter: Technical Information
Si
auxiliary contacts, silver plated
terminals one each N/O and N/C
Current ratings
Voltage rating
AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 80 V)
0.05...16 A
Current rating range
Auxiliary circuit
Typical life
0.05...16 A
1 A, AC 240 V / DC 65 V
3500 - P10 - Si - 10 A
ordering example
5,000 operations at 1 x IN, inductive
5,000 operations at 2 x IN, resistive
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Ambient temperature
-30...+60 °C (-22...+140 °F)
Insulation co-ordination
(IEC 60664 and 60664 A) withstand voltage
2.5 kV
rated impulse
pollution
degree
2
Standard current ratings and typical internal resistance values
reinforced insulation in operating area
Current
Internal
Current
Internal
Dielectric strength
(IEC 60664 and 60664A)
operating area
main/aux. circuit
aux. circuit 4-5/6-7
rating (A)
resistance (Ω) rating (A)
resistance (Ω)
test voltage
AC 3,000 V
AC 1,500 V
AC 840 V
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
447
131
40
3
0.19
4
0.090
0.061
0.041
0.034
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
Insulation resistance
> 100 MΩ (DC 500 V)
5
Interrupting capacity Icn
0.05...0.8 A self-limiting
19.3
10.4
7.1
6
1...2 A
2.5...16 A
200 A
400 A
7
Interrupting capacity
(UL 1077)
IN
UN
AC 250 V
DC 80 V
8
0.05...16 A
0.05...16 A
1,000 A
1,000 A
4.3
10
12
14
15
16
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP00
2.5
Vibration
5 g (57-500 Hz), 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
1.67
0.61
0.38
0.24
1.5
2
Shock
25 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
2.5
Humidity
Mass
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Approvals
approx. 40 g
Authority Standard
Rated voltage
Current ratings
AC 240 V
DC 65 V
0.05...16 A
0.05...16 A
VDE
IEC/EN 60934
AC 250 V
DC 80 V
0.05...16 A
0.05...16 A
UL
UL 1077
C22.2 No 235
AC 250 V
DC 80 V
0.05...16 A
0.05...16 A
CSA
C22.2 No 235
1646
www.e-t-a.de
1