Thermal-Magnetic Circuit Breakers 3300/3400
Description
Single pole thermal-magnetic circuit breakers with tease-free, trip-free,
press-to-reset, snap action mechanism (R-type TM CBE to EN 60934;
M-type with manual release (-H). Available with fast acting and standard
magnetic tripping characteristics - types 3300 and 3400 - both with
threadneck panel mounting. Options include auxiliary contacts, a
separate shunt tap terminal (-A3), and pull-to-trip manual release (-H).
Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Control systems, instrumentation, medical equipment, machine tools,
robotics.
1
3300
3400
fast acting
standard delay
Ordering information 3300
Technical data
Type No.
3300 fast acting
For further details please see chapter: Technical Information
Mounting
Voltage rating
AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 80 V)
iG2 moulded threadneck M12x1, > 5 pcs: hex nut and knurled nut
bulk shipped
Terminal design
P10 blade terminals tin-plated DIN 46244-A6.3-0.8
Current ratings
Auxiliary circuit
0.05...16 A
1 A, AC 240 V / DC 65 V
Current ratings
0.05...16 A
Typical life
with -H:
5,000 operations at 1 x IN, inductive
5,000 operations at 2 x IN, resistive
3300 - iG2 - P10 -10 A
without -H: 0.05...8 A 5,000 operations at 2 x IN, inductive
> 8 A
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664 A) withstand voltage
operating area
1,500 operations at 2 x IN, inductive
-30...+60 °C (-22...+140 °F)
Ordering information 3400
rated impulse
pollution
degree
2
Type No.
3400 standard delay
2.5 kV
reinforced insulation in operating area
Mounting
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area
main circuit/aux. circuit AC 1,500 V
aux. circuit 4-5/6-7
Insulation resistance
Interrupting capacity Icn
iG2 moulded threadneck M12x1 (bulk-shipped), not with -H;
...
leave blank for metal threadneck, required for -H
Terminal design
AC 3,000 V double insulation
P10 blade terminals 6.3-0.8 (QC .250)
K20 screw terminals M3.5x5.5 with clamp (not for -Si and -A3)
Shunt terminal (optional)
AC 840 V
> 100 MΩ (DC 500 V)
A3 same as main terminals, up to IN=7 A max. load 5 A
Manual release (optional)
0.05...0.8 A
1...2 A
2.5...16 A
self-limiting
200 A
400 A
H
manual release facility (pull), without
reinforced insulation in operating area,
for M12x1 metal threadneck only.
Metal threadneck version for -H is not approved.
Auxiliary contacts (optional)
Si with silver-plated solder terminals
(N/O and N/C)
Interrupting capacity
(UL 1077)
IN
UN
0.05...16 A
0.05...16 A
AC 250 V 1,000 A
DC 80 V
1,000 A
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP00
Current ratings
0.05...16 A
Vibration
5 g (57-500 Hz), 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
3400 - iG2 - P10 - .. - .. - Si -10 A
3400 - ... - P10 - .. - H - Si - 10 A
ordering example, without manual
release and with moulded
threadneck
ordering example, with manual
release and metal threadneck
Shock
25 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity
Mass
240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
3300: approx. 55 g
3400: approx. 50 g
Approvals
Authority Standard
Rated voltage
Current ratings
VDE
IEC/EN 60934 AC 240 V
0.05...16 A
0.05...16 A
DC 65 V
UL
UL 1077
C22.2 No 235
AC 250 V
DC 80 V
0.05...16 A
0.05...16 A
CSA
C22.2 No 235 AC 250 V
DC 80 V
0.05...16 A
0.05...16 A
1629