MINI MCR-2-UI-UI(-PT)(-C)
3-way signal conditioner
Data sheet
106006_en_02
© PHOENIX CONTACT 2016-02-10
1
Description
The 3-way signal conditioner with pluggable connection
technology and calibrated measuring range changeover
can be configured using DIP switches and is used for the
electrical isolation, conditioning, amplification, and filtering
of unipolar and bipolar standard and normalized signals.
On the input side, the standard analog signals 0 - 20 mA,
4 - 20 mA, 0 - 10 V, 0 - 5 V, 1 - 5 V, or -10 - 10 V and the
signals 2 - 10 V, 0 - 20 V, 4 - 20 V, 0 - 24 V, 4.8 - 24 V,
6 - 30 V, 0 - 30 V, -5 - 5 V, -20 - 20 V, -24 - 24 V, -30 - 30 V,
and -20 - 20 mA are available.
On the output side, 0 - 20 mA, 4 - 20 mA, 0 - 10 V, 2...10 V,
0 - 5 V, 1 - 5 V, -10 - 10 V, and -5 - 5 V are available.
Features
–
Configurable 3-way signal conditioner with plug-in
connection technology
–
Input and output signal range and cut-off frequencies
configurable via DIP switches
–
–
–
–
–
–
Calibrated measuring range switch-over
Approval for Ex-zone 2 (nA)
Screw or push-in connection available
Can be supplied configured or unconfigured
Reinforced insulation according to IEC 61010-1
Supply voltage range 9.6 ... 30 V DC
There is no need for adjustment following a measuring
range changeover.
WARNING: Correct usage in potentially explosive areas
The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided
here during installation and observe the information in the "Safety regulations and installation notes".
This device offers the option of NFC communication.
You can use the MINI Analog Pro Smartphone app to call-up DIP switch setting help and comprehensive
module information via the NFC interface of your Smartphone.
The MINI Analog Pro Smartphone app is available to you free.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
This document is valid for the products listed in the “Ordering data”.