MODEL: 27RS
Head-mounted Two-wire Signal Conditioners
27-UNIT
RELATED PRODUCTS
• USB interface Bell202 modem (model: COP-HU)
Usable in ‘non-hazardous’ area only.
• PC configurator software (model: 27MCFG)
Downloadable at M-System’s web site.
RTD TRANSMITTER
(PC programmable)
Functions & Features
GENERAL SPECIFICATIONS
Construction: Sensor head-mounting
Connection: M3 screw terminals (torque 0.5 N·m)
Screw terminal: Nickel-plated brass
Housing material: Flame-resistant resin (black)
Isolation: Input to output
• Accepts direct input from an RTD and provides a standard
4 – 20 mA DC signal
• Suitable for Functional Safety applications up to SIL2
• I/O range programming via PC Configurator
• User’s temperature table can be used
• Self diagnostics
Function monitor LED: Input status and error status are
displayed by blinking mode.
User-configurable items: PC and the transmitter are
connected with the COP-HU.
• Input sensor type
• Low temperature drift
44 (1.73) DIA.
• Number of wires
• Input range
20.7
(.81)
• Burnout
• Output limits (Upper / Lower)
• Damping time (factory set to 0)
• Linearization
mm (inch)
• Output calibration
• Loop test output
MODEL: 27RS–[1][2]
INPUT SPECIFICATIONS
The input is factory set for use with Pt 100 (JIS ’97, IEC),
0 to 100°C.
ORDERING INFORMATION
• Code number: 27RS-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. 27RS-0/M)
■ RTD (2-wire, 3-wire or 4-wire)
Input resistance: ≥ 1 MΩ
Use Ordering Information Sheet (No. ESU-7653). Factory
standard setting will be used if not otherwise specified.
Specify the country in which the product is to be used with
the Safety Approval code 2.
Excitation: 0.2 mA
Allowable leadwire resistance: Max. 10 Ω per wire
Temperature Range
RTD
MIN. SPAN
USABLE RANGE
-200 to +850
-328 to +1562
-200 to +850
-328 to +1562
-200 to +850
-328 to +1562
-200 to +510
-328 to +950
10
18
10
18
10
18
10
18
°C
°F
°C
°F
°C
°F
°C
°F
Pt 100 (JIS '97, IEC)
[1] SAFETY APPROVAL
0: None
Pt 500
1: FM intrinsically safe
Pt 1000
(Option code /M is not selectable)
2: ATEX intrinsic safety
JPt 100 (JIS '89)
(Option code /M is not selectable)
OUTPUT SPECIFICATIONS
Output range: 4 – 20 mA DC
[2] OPTIONS
Function Monitor LED
Blank: Without
Operational range: 3.75 – 23 mA
Load resistance vs. supply voltage:
/M: With
Load Resistance (Ω) = (Supply Voltage (V) – 9 (V)) ÷ 0.023
(A) (including leadwire resistance)
Burnout: 3.75 – 3.8 mA or 21.5 – 23 mA
(factory set to 23 mA)
27RS SPECIFICATIONS
ES-7653 Rev.8 Page 1/4
http://www.m-system.co.jp/