24A34 Series
Fan/Heat Sequencers
INSTALLATION INSTRUCTIONS
FAILURETO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
The 24A34 Series Fan/Heat Sequencer gives the service tech-
nician a direct replacement for sequencing both fan and heat.
The terminal markings on the 24A34 sequencers are equivalent
to most other manufacturers’ types.
These sequencers may be wired in series, as shown in wiring
diagrams, to allow sequencing of one through seven element
furnaces.
CAUTION
!
To prevent electrical shock and/or equipment damage,
disconnect electric power to system, at main fuse or
circuit breaker box, until installation is complete.
Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could cause
shock or fire hazard.
SPECIFICATIONS
Electrical Ratings - Single Load Contact Ratings (All Models)
Resistive (Non-Inductive) Motor Ratings (Inductive)
VAC
120
240
480
Watts
3000
6000
6000
Amps
25.0
Full Load
14.0A
7.0A
Locked Rotor
Pilot Duty
125 VA
72.0A
42.0A
–
25.0
125 VA
12.5
–
480 VA
Electrical Ratings - Single Load Contact Ratings (All Models)
Timings – ON
Timings – OFF
Model
Number
Timings Switches M1-M2 M3-M4 M5-M6 M7-M8 M9-M10 M1-M2 M3-M4 M5-M6 M7-M8 M9-M10
40-110
–
–
–
–
–
–
–
24A34-1
24A34-2
1
1
1
1
2
2
4
1
1
1
2
2
3
4
5
1
1-20
–
–
–
–
30-90
–
–
–
–
–
–
–
–
–
–
1-30
–
–
40-110 40-110
–
–
1-20
–
1-20
–
24A34-3 ➀
24A34-4
♦
♦
–
–
1-30
1-110
1-30
–
–
30-90 30-90
♦
♦
1-110 1-110
–
–
1-110 1-110 1-110
–
24A34-5 ➀
24A34-6 ➀
24A34-14 ➀➁
24A34-15
♦
♦
1-110 1-110
1-110 1-110
♦
1-110 1-110 1-110 1-110
♦
♦
♦
1-160 1-160 1-160 1-160
1-160
–
1-160 1-160 1-160 1-160 1-160
♦
♦
75-95
–
–
–
1-60
–
–
–
–
TABLE NOTES:
➀ M1-M2 and M3-M4 are always first switches to turn ON and last to turn OFF. All other switches are random ON and random OFF
➁ 24A34-14 Switch contacts designated F1 - F2 instead of M1 - M2
♦ These contacts switch simultaneously
NOTE: Underwriters Laboratories requires a fan interlock circuit to insure the blower remains operating whenever more than one sequencer is used. The fan in-
terlock should be the M1 / M2 contacts of the second or third sequencer. All M1 / M2 contacts are wired to the blower motor so that any sequencer that is energized
will keep the blower ON.
PART NO. 37-4800C
Replaces 37-4800B
1050
www.white-rodgers.com