24A34 Series  
Fan/Heat Sequencers  
INSTALLATION INSTRUCTIONS  
FAILURETO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE  
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL  
INJURY AND/OR PROPERTY DAMAGE.  
DESCRIPTION  
The 24A34 Series Fan/Heat Sequencer gives the service tech-  
nician a direct replacement for sequencing both fan and heat.  
The terminal markings on the 24A34 sequencers are equivalent  
to most other manufacturers’ types.  
These sequencers may be wired in series, as shown in wiring  
diagrams, to allow sequencing of one through seven element  
furnaces.  
CAUTION  
!
To prevent electrical shock and/or equipment damage,  
disconnect electric power to system, at main fuse or  
circuit breaker box, until installation is complete.  
Do not use on circuits exceeding specified voltage.  
Higher voltage will damage control and could cause  
shock or fire hazard.  
SPECIFICATIONS  
Electrical Ratings - Single Load Contact Ratings (All Models)  
Resistive (Non-Inductive) Motor Ratings (Inductive)  
VAC  
120  
240  
480  
Watts  
3000  
6000  
6000  
Amps  
25.0  
Full Load  
14.0A  
7.0A  
Locked Rotor  
Pilot Duty  
125 VA  
72.0A  
42.0A  
25.0  
125 VA  
12.5  
480 VA  
Electrical Ratings - Single Load Contact Ratings (All Models)  
Timings ON  
Timings OFF  
Model  
Number  
Timings Switches M1-M2 M3-M4 M5-M6 M7-M8 M9-M10 M1-M2 M3-M4 M5-M6 M7-M8 M9-M10  
40-110  
24A34-1  
24A34-2  
1
1
1
1
2
2
4
1
1
1
2
2
3
4
5
1
1-20  
30-90  
1-30  
40-110 40-110  
1-20  
1-20  
24A34-3 ➀  
24A34-4  
1-30  
1-110  
1-30  
30-90 30-90  
1-110 1-110  
1-110 1-110 1-110  
24A34-5 ➀  
24A34-6 ➀  
24A34-14 ➀➁  
24A34-15  
1-110 1-110  
1-110 1-110  
1-110 1-110 1-110 1-110  
1-160 1-160 1-160 1-160  
1-160  
1-160 1-160 1-160 1-160 1-160  
75-95  
1-60  
TABLE NOTES:  
M1-M2 and M3-M4 are always first switches to turn ON and last to turn OFF. All other switches are random ON and random OFF  
24A34-14 Switch contacts designated F1 - F2 instead of M1 - M2  
These contacts switch simultaneously  
NOTE: Underwriters Laboratories requires a fan interlock circuit to insure the blower remains operating whenever more than one sequencer is used. The fan in-  
terlock should be the M1 / M2 contacts of the second or third sequencer. All M1 / M2 contacts are wired to the blower motor so that any sequencer that is energized  
will keep the blower ON.  
PART NO. 37-4800C  
Replaces 37-4800B  
1050  
www.white-rodgers.com  
www.emersonclimate.com  

与24A34-1相关器件

型号 品牌 获取价格 描述 数据表
24A34-14 ETC

获取价格

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
24A34-15 ETC

获取价格

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
24A34-2 ETC

获取价格

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
24A34-3 ETC

获取价格

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
24A34-4 ETC

获取价格

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
24A34-5 ETC

获取价格

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
24A34-6 ETC

获取价格

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
24AA00 MICROCHIP

获取价格

128 Bit I 2 C? Bus Serial EEPROM
24AA00/MC MICROCHIP

获取价格

16 X 8 I2C/2-WIRE SERIAL EEPROM, PDSO8, 2 X 3 MM, 0.90 MM HEIGHT, LEAD FREE, PLASTIC, MO-2
24AA00/MCG MICROCHIP

获取价格

16 X 8 I2C/2-WIRE SERIAL EEPROM, PDSO8, 2 X 3 MM, 0.90 MM HEIGHT, LEAD FREE, PLASTIC, MO-2