5秒后页面跳转
233P-1.5-ENCL PDF预览

233P-1.5-ENCL

更新时间: 2023-12-06 20:12:57
品牌 Logo 应用领域
力特 - LITTELFUSE /
页数 文件大小 规格书
4页 490K
描述
The 233P1.5-ENCL is an enclosed single-phase pump monitor with an input voltage value of 230 V ac, an input load range of ?–1.5 hp, and an output load rating of 1.5 hp @ 240 V ac (10 A maximum).

233P-1.5-ENCL 数据手册

 浏览型号233P-1.5-ENCL的Datasheet PDF文件第2页浏览型号233P-1.5-ENCL的Datasheet PDF文件第3页浏览型号233P-1.5-ENCL的Datasheet PDF文件第4页 
Motor and Pump Protection Relays  
233P Series  
Single-Phase Pump Monitor  
Description  
The Littelfuse models 111P (115 volt, 1⁄  
3
to 1hp); 233P-1.5 (230 volt, 1⁄  
3
to 1.5hp); and 233P (230 volt, 1⁄  
to 3hp) are single-  
3
phase pump monitors used in a variety of applications to protect from dry-well, dead-head, jammed impeller, rapid-cycling,  
overvoltage, and undervoltage conditions.  
Operation  
A calibration adjustment allows the unit to be calibrated to your specific pumping applications, which reduces the possibility  
of false or nuisance tripping. A unique microcontroller-based voltage and current-sensing circuit constantly monitor the  
incoming power for fluctuations, overcurrent, and undercurrent conditions. When an abnormality, such as loss of suction,  
is detected, the product deactivates its output relay and directly disconnects the pump motor. The relay then begins its  
user-selectable restart delay (dry-well recovery) timer. When the timer counts to zero or power is removed and reapplied,  
the relay reactivates its output relay and turns the pump back on. The infrared LED communicates with a hand-held  
diagnostics tool called the Informer* (sold separately). The Informer displays parameters including calibration points, trip  
points, run time and last faults.  
There are special considerations for pump cables larger than #10 AWG: In some cases where larger motors are installed  
with deep-set pumps, pump cables are used that exceed the relay’s terminal size. In these conditions, a short splice of  
#10 AWG or #12 AWG may be a solution at the control box. Note: All local, state, and national electric codes should be  
followed when applying this solution.  
Note: The description and operations apply to Littelfuse models 111P (115 V, 1⁄  
3
to 1 hp); 233P-1.5 (230 V, 1⁄  
3
to 1.5 hp); and 233P (230 V, 1⁄  
to 3 hp). These models have a sensitivity  
3
adjustment for the dry-well trip point. After calibration is complete, you can adjust the sensitivity for the dry-well/dead-head trip point from 70-90 % of the full load. This makes the  
unit even more adaptable to varying pumping applications. If you have a very low producing well, you increase the sensitivity closer to the 90 % mark, or if you have a very heavy  
producing well, you should decrease the sensitivity around the 70 % mark.  
*Informer: A hand-held diagnostic tool that uses an infrared receiver to access information that can be helpful for troubleshooting the system.  
Features & Benefits  
FEATURES  
BENEFITS  
Constant monitoring of voltage, power factor, and current for reliable  
pump protection  
Proprietary microcontroller-based circuitry  
Calibrates unit to your specific individual pumping application and  
reduces nuisance tripping  
Onboard calibration process  
User-adjustable sensitivity knob makes the unit more adaptable to  
varying pumping applications  
Onboard sensitivity adjustment  
Littelfuse.com/233P  
©2022 Littelfuse, Inc.  
Specifications are subject to change without notice.  
1 of 4  
Revised: 09/30/2022  

与233P-1.5-ENCL相关器件

型号 品牌 描述 获取价格 数据表
233P-ENCL LITTELFUSE The 233P-ENCL is an enclosed single-phase pum

获取价格

233R3 CANDD Bobbin Wound Surface Mount Inductors

获取价格

233R3C MURATA Bobbin Wound Surface Mount Inductors

获取价格

233S1 ETC CABLE R/A SGL-END FMALE 3POS 1M

获取价格

233S2 ETC CABLE R/A SGL-END FMALE 3POS 2M

获取价格

233S4 ETC CABLE R/A SGL-END FMALE 3POS 4M

获取价格