DIESEL GENERATOR SET
2250-XC6DT2
/
/
2250 kWe 60 Hz Standby
380 - 13.8kV
(Reference 2045-XC6DT2 for Prime Rating Technical Data)
SYSTEM RATINGS
Standby
Voltage (L-L) 380V
480V**
3
600V
3
4160V
3
12470V
3
13200V
3
13800V
3
Phase
3
PF
0.8
0.8
0.8
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
60
60
kW
kVA
Amps
2250
2813
4278
2250
2812.5
3383
2250
2812.5
2706
2250
2812.5
390
2250
2812.5
130
2250
2812.5
123
2250
2812.5
118
skVA@30%
Voltage Dip
Generator
Model*
Temp Rise
Connection
3625
8400
3900
5000
C/F
C/F
C/F
1020FDL1102
130 °C/40 °C 130 °C/40 °C
6 LEAD WYE 4 BAR WYE
744RSL4058
1020FDS1013
130 °C/40 °C
6 LEAD WYE
744FSM4376
130 °C/40 °C
6 LEAD WYE
1020FDH5584
130 °C/40 °C
6 LEAD WYE
1020FDH5584 1020FDH5584
130 °C/40 °C 130 °C/40 °C
6 LEAD WYE
6 LEAD WYE
* Consult the factory for alternate configuration.
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
//ꢀ
Emissions – EPA Tier 2 Certified
//ꢀ
Performance Assurance Certification (PAC)
//ꢀ
Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//ꢀ
//ꢀ
//ꢀ
Seismic Certification – Optional
– IBC Certification
– OSHPD Pre-Approval
Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 85%.
UL 2200 Listed – Optional