Thermal-Magnetic Circuit Breaker 2215-L.../G...
Description
Miniaturised single pole thermal-magnetic circuit breakers with trip-free
mechanism and toggle actuation (S-type TM CBE to EN 60934). Two
designs provide the option of either printed circuit board or threadneck
panel mounting. A separate shunt tap terminal and auxiliary contacts
are available. Fast acting, medium or long delay characteristics can be
specified for both models.
Suitable for use in distribution rails – see section Power Distribution
Systems.
Complies with CBE standard EN 60934 (IEC 60935).
Typical applications
1
2215-L1..
Technical data
2215-G1...
Control equipment, communications systems, instrumentation.
Suitable for mounting on Euro cards.
Ordering information 2215-G1
Voltage rating
AC 250 V (50/60 Hz); DC 50 V
(UL: AC 250 V; DC 75 V)
Type No.
2215 single pole thermal-magnetic circuit breaker
Mounting
Current rating range
0.05...10 A
(higher current ratings to special order)
G1 threadneck panel mounting
Number of poles
Auxiliary circuit
1 A, AC 250 V / DC 28 V
10,000 operations at 1 x IN
-30...+60 °C (-22...+140 °F)
Typical life
1 1-pole protected
Mounting hardware
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664 A) withstand voltage
2.5 kV
1
2 hex nuts 1/4“-40 UNS-2A, serrated washer,
location pin (-G1 only)
rated impulse
pollution
degree
2
Terminal design (main contacts)
P1 blade terminals 6.3-0.8, without shunt terminal
Characteristic curve
reinforced insulation in operating area
Dielectric strength
IEC 60664 and 60664A)
operating area
F1 fast acting:1.01-1.4xIN; magn.2-4xIN DC (DC only)
M1 standard delay: therm. 1.01-1.4xIN;
magn. 4.5-10.5xIN DC; magn. 3.5-8xIN AC
T1 delayed: therm. 1.01-1.4xIN; DC
magn. 8-17xIN DC, 6-13xIN AC
test voltage
AC 3,000 V
AC 1,500 V
main/aux. circuit
Insulation resistance
> 100 MΩ (DC 500 V)
300 A
Auxiliary contacts
Interrupting capacity Icn
S0
S11
without auxiliary contact
with auxiliary contact (change over)
blade terminals 6.3x0.8 (QC .250)
Current ratings
Interrupting capacity
(UL 1077)
IN
UN
0.05 A
0.1...6 A
8...10 A
0.05...10 A
AC 250 V
AC 250 V
AC 250 V
DC 50 V
200 A
1,000 A
2,000 A
1,000 A
0.05...10 A
2215 - G1 1 1 - P1 F1 -S11 - 0.5 A
ordering example
Degree of protection
(IEC 60529/DIN 40050)
operating area IP30
terminal area IP00
Vibration
curve F1:
curves M1, T1:
Ordering information 2215-L1
6 g (57-500 Hz), 0.46 mm (10-57 Hz)
8 g (57-500 Hz), 0.61 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
Type No.
2215 single pole thermal-magnetic circuit breaker
Mounting
10 frequency cycles/axis
Shock
L1 PCB mounting
curves F1, M1, T1:
curve F1:
curves M1, T1:
30 g (11 ms), directions 1, 2, 3, 4, 5,
10 g (11 ms), direction 6
15 g (11 ms), direction 6
Number of poles
1 1-pole protected
Mounting hardware
to IEC 60068-2-27, test Ea
0
without accessories
Terminal design (main contacts)
L1 solder pins, without shunt terminal
Characteristic curve
Corrosion
Humidity
Mass
96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
F1 fast acting:1.01-1.4xIN; magn.2-4xIN DC (DC only)
M1 standard delay: therm. 1.01-1.4xIN;
magn. 4.5-10.5xIN DC; magn. 3.5-8xIN AC
Auxiliary contacts - terminal design
approx. 25 g
S0
S12
without auxiliary contact
with auxiliary contact (change over)
solder pins
Approvals
Current ratings
0.05...10 A
Authority
Standard
Rated voltage
Current ratings
UL
UL 1077
AC 250 V
DC 75 V
0.05 A…10 A
0.05 A…10 A (20 A)
2215 - L1 1 0 - L1 F1 -S12 - 0.5 A ordering example
CSA
C22.2 No.
235
AC 250 V
DC 75 V
0.05 A…10 A
0.05 A…10 A (20 A)
1633
www.e-t-a.de
1