UL-Series - UL489 Miniature Molded Case Circuit Breaker - 1 pole C-Trip - AC
1.05-1.35xIN
Rated
Current
0.3A
0.5A
1.0A
1.6A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
Type/
Cat. No.
1C03UL
1C05UL
1C1UL
1C1.6UL
1C2UL
1C3UL
1C4UL
1C5UL
1C6UL
1C8UL
1C10UL
1C12UL
1C13UL
1C15UL
1C16UL
1C20UL
1C25UL
1C30UL
1C32UL
1C40UL
1C50UL
1C60UL
1C63UL
Rated
Voltage
60
40
C
US
LISTED
C.B.
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
277V AC
240V AC
240V AC
240V AC
240V AC
10
4
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
E329510
One Pole
1
10
4
1
0.4
10-1
4x10-2
10-2
4x10-3
10-3
Standard Pack: 12
1
2
3
4 5 6 8 10
20
40
100
Weight:
0.3-32A:
1.74kg (3.83lb.)
Multiple of Rated Current
40A
50A
60A
63A
0.3A Through 10A Rated Current
40-63A:
1.98kg (4.37lb.)
1.05-1.35xIN
60
40
10
4
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
0.3 - 63A/ 240V AC, 0.3-32A/ 277V AC*
40ºC (104ºF)
Current/ Voltage Rating
Calibration Temperature
Ambient Temperature
Storage Temperature
Terminal Torque (min/max)
Electrical Life
1
-25ºC to +55ºC (-13ºF to 131ºF )
-40ºC to +70ºC (-40ºF to 158ºF )
2 Nm (17.7 lb.in.) / 2.5Nm (22.2 lb.in)
6000 switching cycles ON/ OFF
10000 switching cycles ON/ OFF
> 15g according to DIN EN 60069-2-59 during a load
with I = 1.05 x I
10
4
1
0.4
Mechanical Life
10-1
Vibration Resistance
4x10-2
1
N
10-2
25g @ 11ms
Resistance to mechanical shocks
*One device dual voltage ratings.
4x10-3
10-3
1
2
3
4 5 6 8 10
20
40
100
Multiple of Rated Current
51.5 mm
7
37.5 mm
25.5 mm
12A Through 63A Rated Current
“C” Magnetic Trip Parameters
6
Rated current 0.3A to 63A.
1. Hold for a minimum of 100ms at surge of 5 times rated current.
2. Trip in under 100ms at 10 times rated current.
Short Circuit Interrupting Capacity
AC
No.
Poles
Type
03-32A
33-63A
1
AC
10kA @ 120, 240,
277V
10kA @ 120,
240V
8
4
17.5 mm
1 Pole
14.5 mm
30.5 mm
51.5 mm
68.4 mm